Sizing

gtbair-hyg

Hygienic Airflow

Hygienic airflow calculation — French labour code & ERP (public buildings).

  • rt2012
  • re2020
  • erp
Project

Total fresh air flow

385m³/h

106.9 L/s · extract 0 m³/h

Overall verdict

Acceptable

Supply/extract balance 100 % · Mean CO₂ 1,400 ppm

1 room · 25 occupants · 3 warnings

Primary school classroom

Education · 60 m² · 180 m³

385m³/h

n = 2.1 ACH · CO₂ 1,400 ppm

Teacher
French Labour Code Art. R4222-6 — offices, premises without physical work
1 × 2525 m³/h
Pupils
RSDT Art. 64.1 — nursery, primary and lower secondary education (middle school)
24 × 15360 m³/h
NF EN 16798 (bldg. cat. B2) : IAQ 1 : 1,209 m³/h · IAQ 2 : 846 m³/h · IAQ 3 : 483 m³/h FR / IAQ 2 ratio : 46 %

Warnings

  • Equilibrium CO₂ 1400 ppm > 1300 ppm: ventilation insufficient against good practice.
  • French airflow 385 m³/h is 46 % of the European IAQ 2 standard (846 m³/h).
  • Supply/extract imbalance: 100.0 % (tolerance ±10 %).
Applied legal texts
  • · French Labour Code R4222-6
  • · RSDT 64.1

Hygienic ventilation airflow — regulatory calculation for commercial buildings

Calculation of the minimum fresh air flow to supply to a room or building under the French Labour Code (R4222-6, R4212-6), the model departmental sanitary regulations (RSDT 64.1 public-access buildings with non-specific pollution, RSDT 64.2 specific pollution from commercial kitchens and sanitary facilities), the order of 31 August 2021 for nurseries, the NF S 90-351 standard for infection-risk zones in healthcare, and comparison with EN 16798-1 method 1. Scope: commercial, public-access buildings, healthcare, education, catering, sports, industry. Residential out of scope.

Calculations run locally in your browser. No data is sent to our servers.