Electricity meter RTU 50 registers To check

To check

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Source

upstream: jibrilsharafi · fba9d46

original doc

Writes

0

Scaled

0

Enums

0

Multi-register

19

Registers (50/50)

scaleunit
0x0001 (1)holdingPhase-B-voltage uint16 VR
0x0002 (2)holdingPhase-C-voltage uint16 VR
0x0003 (3)holdingLine-ab-voltage uint16 VR
0x0004 (4)holdingLine-bc-voltage uint16 VR
0x0005 (5)holdingLine-ca-voltage uint16 VR
0x0006 (6)holdingPhase-A-current uint16 AR
0x0007 (7)holdingPhase-B-current uint16 AR
0x0008 (8)holdingPhase-C-current uint16 AR
0x0009 (9)holdingNeutral-current uint16 AR
0x000A (10)holdingTotal-active-power int32 ×2 WR
0x000C (12)holdingTotal-reactive-power int32 ×2 VarR
0x000E (14)holdingTotal-power-factor int16 R
0x000F (15)holdingPhase-A-active-power int16 WR
0x0010 (16)holdingPhase-B-active-power int16 WR
0x0011 (17)holdingPhase-C-active-power int16 WR
0x0012 (18)holdingPhase-A-reactive-power int16 WR
0x0013 (19)holdingPhase-B-reactive-power int16 WR
0x0014 (20)holdingPhase-C-reactive-power int16 WR
0x0015 (21)holdingPhase-A-power-factor int16 R
0x0016 (22)holdingPhase-B-power-factor int16 R
0x0017 (23)holdingPhase-C-power-factor int16 R
0x0018 (24)holdingFrequency uint16 HzR
0x0019 (25)holdingTotal-active-energy uint32 ×2 kWhR
0x001B (27)holdingTotal-reactive-energy uint32 ×2 kvarhR
0x001D (29)holdingInput-active-energy uint32 ×2 kWhR
0x001F (31)holdingOutput-active-energy uint32 ×2 kWhR
0x0021 (33)holdingInput-reactive-energy uint32 ×2 kvarhR
0x0023 (35)holdingOutput-reactive-energy uint32 ×2 kvarhR
0x0025 (37)holdingOn-off-status uint16 R
0x0026 (38)holdingRelay-status uint16 R
0x0027 (39)holdingAlarm-status uint16 R
0x0028 (40)holdingCt-ratio uint16 R
0x002A (42)holdingAverage-phase-voltage uint16 VR
0x002B (43)holdingAverage-line-voltage uint16 VR
0x002C (44)holdingAverage-phase-current uint16 AR
0x002D (45)holdingCurrent-unbalance-rate uint16 AR
0x002E (46)holdingPhase-A-apparent-power uint16 VAR
0x002F (47)holdingPhase-B-apparent-power uint16 VAR
0x0030 (48)holdingPhase-C-apparent-power uint16 VAR
0x0031 (49)holdingTotal-apparent-power uint32 ×2 R
0x0033 (51)holdingGrid-input-active-energy uint32 ×2 kWhR
0x0035 (53)holdingGrid-output-active-energy uint32 ×2 R
0x0037 (55)holdingGrid-total-active-energy uint32 ×2 R
0x0039 (57)holdingGrid-input-reactive-energy uint32 ×2 kvarhR
0x003B (59)holdingGrid-output-reactive-energy uint32 ×2 kvarhR
0x003D (61)holdingGrid-totalreactive-energy uint32 ×2 kvarhR
0x003F (63)holdingGenerator-input-active-energy uint32 ×2 kWhR
0x0041 (65)holdingGenerator-output-active-energy uint32 ×2 kWhR
0x0043 (67)holdingGenerator-total-active-energy uint32 ×2 kWhR
0x0045 (69)holdingGenerator-input-reactive-energy uint32 ×2 kvarhR