electric-pm600

Electricity meter RTU 50 registers To check

To check

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont

Source

upstream: jibrilsharafi · fba9d46

original doc

Writes

0

Scaled

0

Enums

0

Multi-register

0

Registers (50/50)

scaleunit
0x03E7 (999)holdingUpdate-interval int16 R
0x03E8 (1000)holdingFrequency int16 HertzR
0x03EA (1002)holdingCurrent,-phase-A int16 AmpsR
0x03EB (1003)holdingCurrent,-phase-B int16 AmpsR
0x03EC (1004)holdingCurrent,-phase-C int16 AmpsR
0x03ED (1005)holdingCurrent,-calculated-neutral int16 AmpsR
0x03F1 (1009)holdingCurrent-unbalance,-phase-A int16 PercentR
0x03F2 (1010)holdingCurrent-unbalance,-phase-B int16 PercentR
0x03F3 (1011)holdingCurrent-unbalance,-phase-C int16 PercentR
0x03F4 (1012)holdingCurrent-unbalance,-worst int16 PercentR
0x03F5 (1013)holdingVoltage,-phase-A-to-B int16 VoltsR
0x03F6 (1014)holdingVoltage,-phase-B-to-C int16 VoltsR
0x03F7 (1015)holdingVoltage,-phase-C-to-A int16 VoltsR
0x03F9 (1017)holdingVoltage,-phase-A-to-neutral int16 VoltsR
0x03FA (1018)holdingVoltage,-phase-B-to-neutral int16 VoltsR
0x03FB (1019)holdingVoltage,-phase-C-to-neutral int16 VoltsR
0x03FD (1021)holdingVoltage-unbalance,-phase-A-B int16 PercentR
0x03FE (1022)holdingVoltage-unbalance,-phase-B-C int16 PercentR
0x03FF (1023)holdingVoltage-unbalance,-phase-C-A int16 PercentR
0x0400 (1024)holdingVoltage-unbalance,-L-L-worst int16 PercentR
0x0401 (1025)holdingVoltage-unbalance,-phase-A int16 PercentR
0x0402 (1026)holdingVoltage-unbalance,-phase-B int16 PercentR
0x0403 (1027)holdingVoltage-unbalance,-phase-C int16 PercentR
0x0404 (1028)holdingVoltage-unbalance,-L-N-worst int16 PercentR
0x0406 (1030)holdingTrue-power-factor,-phase-A int16 R
0x0407 (1031)holdingTrue-power-factor,-phase-B int16 R
0x0408 (1032)holdingTrue-power-factor,-phase-C int16 R
0x0409 (1033)holdingTrue-power-factor,-3-phase-total int16 R
0x040E (1038)holdingReal-power,-phase-A int16 kWR
0x040F (1039)holdingReal-power,-phase-B int16 kWR
0x0410 (1040)holdingReal-power,-phase-C int16 kWR
0x0411 (1041)holdingReal-power,-3-phase-total int16 kWR
0x0412 (1042)holdingReactive-power,-phase-A int16 kVArR
0x0413 (1043)holdingReactive-power,-phase-B int16 kVArR
0x0414 (1044)holdingReactive-power,-phase-C int16 kVArR
0x0415 (1045)holdingReactive-power,-3-phase-total int16 kVArR
0x0416 (1046)holdingApparent-power,-phase-A int16 kVAR
0x0417 (1047)holdingApparent-power,-phase-B int16 kVAR
0x0418 (1048)holdingApparent-power,-phase-C int16 kVAR
0x0419 (1049)holdingApparent-power,-3-phase-total int16 kVAR
0x041A (1050)holdingThd/thd-A-current int16 R
0x041B (1051)holdingThd/thd-B-current int16 R
0x041C (1052)holdingThd/thd-C-current int16 R
0x041E (1054)holdingThd/thd-A-voltage int16 R
0x041F (1055)holdingThd/thd-B-voltage int16 R
0x0420 (1056)holdingThd/thd-C-voltage int16 R
0x0435 (1077)holdingA-current-fundamental-rms-magnitude int16 AmpsR
0x07E3 (2019)holdingScale-Factor-A int16 R
0x07E6 (2022)holdingScale-Factor-D int16 R
0x07E7 (2023)holdingScale-Factor-E int16 R