Technical building blocks

gtbmodbus

Modbus Catalogue

Open catalogue of Modbus devices — registers, types, scaling, RTU/TCP.

  • rtu
  • tcp
  • registers

siemens

sentron-pac-3100

Electricity meter RTU 50 registers To check

To check

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Source

upstream: jibrilsharafi · fba9d46

original doc

Writes

0

Scaled

0

Enums

0

Multi-register

50

Registers (50/50)

scaleunit
0x0001 (1)holdingVoltage-a-N float32 ×2 VR
0x0003 (3)holdingVoltage-b-N float32 ×2 VR
0x0005 (5)holdingVoltage-c-N float32 ×2 VR
0x0007 (7)holdingVoltage-a-b float32 ×2 VR
0x0009 (9)holdingVoltage-b-c float32 ×2 VR
0x000B (11)holdingVoltage-c-a float32 ×2 VR
0x000D (13)holdingCurrent-a float32 ×2 AR
0x000F (15)holdingCurrent-b float32 ×2 AR
0x0011 (17)holdingCurrent-c float32 ×2 AR
0x0013 (19)holdingApparent-power-a float32 ×2 VAR
0x0015 (21)holdingApparent-power-b float32 ×2 VAR
0x0017 (23)holdingApparent-power-c float32 ×2 VAR
0x0019 (25)holdingActive-power-a float32 ×2 WR
0x001B (27)holdingActive-power-b float32 ×2 WR
0x001D (29)holdingActive-power-c float32 ×2 WR
0x001F (31)holdingReactive-power-a-(VAR1) float32 ×2 varR
0x0021 (33)holdingReactive-power-b-(VAR1) float32 ×2 varR
0x0023 (35)holdingReactive-power-c-(VAR1) float32 ×2 varR
0x0025 (37)holdingNeutral-current float32 ×2 AR
0x0027 (39)holdingFrequency float32 ×2 HzR
0x002F (47)holdingTotal-apparent-power float32 ×2 VAR
0x0031 (49)holdingTotal-active-power float32 ×2 WR
0x0033 (51)holdingTotal-reactive-power-(VAR1) float32 ×2 varR
0x0035 (53)holdingTotal-power-factor float32 ×2 R
0x0037 (55)holdingMaximum-voltage-a-N float32 ×2 VR
0x0039 (57)holdingMaximum-voltage-b-N float32 ×2 VR
0x003B (59)holdingMaximum-voltage-c-N float32 ×2 VR
0x003D (61)holdingMax.-voltage-a-b float32 ×2 VR
0x003F (63)holdingMax.-voltage-b-c float32 ×2 VR
0x0041 (65)holdingMax.-voltage-c-a float32 ×2 VR
0x0043 (67)holdingMaximum-current-a float32 ×2 AR
0x0045 (69)holdingMaximum-current-b float32 ×2 AR
0x0047 (71)holdingMaximum-current-c float32 ×2 AR
0x0049 (73)holdingMaximum-apparent-power-a float32 ×2 VAR
0x004B (75)holdingMaximum-apparent-power-b float32 ×2 VAR
0x004D (77)holdingMaximum-apparent-power-c float32 ×2 VAR
0x004F (79)holdingMaximum-active-power-a float32 ×2 WR
0x0051 (81)holdingMaximum-active-power-b float32 ×2 WR
0x0053 (83)holdingMaximum-active-power-c float32 ×2 WR
0x0055 (85)holdingMax.-reactive-power-a-(VAR1) float32 ×2 varR
0x0057 (87)holdingMax.-reactive-power-b-(VAR1) float32 ×2 varR
0x0059 (89)holdingMax.-reactive-power-c-(VAR1) float32 ×2 varR
0x005B (91)holdingMax.-neutral-current float32 ×2 AR
0x005D (93)holdingMax.-frequency float32 ×2 HzR
0x0065 (101)holdingMax.-total-apparent-power float32 ×2 VAR
0x0067 (103)holdingMax.-total-active-power float32 ×2 WR
0x0069 (105)holdingMax.-total-reactive-power-(VAR1) float32 ×2 varR
0x006B (107)holdingMax.-total-power-factor float32 ×2 R
0x006D (109)holdingMinimum-voltage-a-N float32 ×2 VR
0x006F (111)holdingMinimum-voltage-b-N float32 ×2 VR
Calculations run locally in your browser. No data is sent to our servers.
open/gtb · MIT · hosted in France
visitors github roadmap messages contact
SYS OK 15/18 tools online uptime — Rack temp 21.3 °C