Technical building blocks

gtbmodbus

Modbus Catalogue

Open catalogue of Modbus devices — registers, types, scaling, RTU/TCP.

  • rtu
  • tcp
  • registers

siemens

sentron-pac-3200

Electricity meter RTU 50 registers To check

To check

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Source

upstream: jibrilsharafi · fba9d46

original doc

Writes

0

Scaled

0

Enums

0

Multi-register

50

Registers (50/50)

scaleunit
0x0001 (1)holdingVoltage-Va-n float32 ×2 VR
0x0003 (3)holdingVoltage-Vb-n float32 ×2 VR
0x0005 (5)holdingVoltage-Vc-n float32 ×2 VR
0x0007 (7)holdingVoltage-Va-b float32 ×2 VR
0x0009 (9)holdingVoltage-Vb-c float32 ×2 VR
0x000B (11)holdingVoltage-Vc-a float32 ×2 VR
0x000D (13)holdingCurrent-a float32 ×2 AR
0x000F (15)holdingCurrent-b float32 ×2 AR
0x0011 (17)holdingCurrent-c float32 ×2 AR
0x0013 (19)holdingApparent-Power-a float32 ×2 VR
0x0015 (21)holdingApparent-Power-b float32 ×2 VR
0x0017 (23)holdingApparent-Power-c float32 ×2 VR
0x0019 (25)holdingActive-Power-a float32 ×2 WR
0x001B (27)holdingActive-Power-b float32 ×2 WR
0x001D (29)holdingActive-Power-c float32 ×2 WR
0x001F (31)holdingReactive-Power-a float32 ×2 vR
0x0021 (33)holdingReactive-Power-b float32 ×2 vR
0x0023 (35)holdingReactive-Power-c float32 ×2 vR
0x0025 (37)holdingPower-Factor-a float32 ×2 -R
0x0027 (39)holdingPower-Factor-b float32 ×2 -R
0x0029 (41)holdingPower-Factor-c float32 ×2 -R
0x002B (43)holdingTHD-R-Voltage-a float32 ×2 %R
0x002D (45)holdingTHD-R-Voltage-b float32 ×2 %R
0x002F (47)holdingTHD-R-Voltage-c float32 ×2 %R
0x0031 (49)holdingTHD-R-Current-a float32 ×2 %R
0x0033 (51)holdingTHD-R-Current-b float32 ×2 %R
0x0035 (53)holdingTHD-R-Current-c float32 ×2 %R
0x0037 (55)holdingFrequency float32 ×2 HR
0x0039 (57)holdingAverage-Voltage-Vph-n float32 ×2 VR
0x003B (59)holdingAverage-Voltage-Vph-ph float32 ×2 VR
0x003D (61)holdingAverage-Current float32 ×2 AR
0x003F (63)holdingTotal-Apparent-Power float32 ×2 VR
0x0041 (65)holdingTotal-Active-Power float32 ×2 WR
0x0043 (67)holdingTotal-Reactive-Power float32 ×2 vR
0x0045 (69)holdingTotal-Power-Factor float32 ×2 -R
0x0047 (71)holdingAmplitude-Unbalance---Voltage float32 ×2 %R
0x0049 (73)holdingAmplitude-Unbalance---Current float32 ×2 %R
0x004B (75)holdingMaximum-Voltage-Va-n float32 ×2 VR
0x004D (77)holdingMaximum-Voltage-Vb-n float32 ×2 VR
0x004F (79)holdingMaximum-Voltage-Vc-n float32 ×2 VR
0x0051 (81)holdingMax.-Voltage-Va-b float32 ×2 VR
0x0053 (83)holdingMax.-Voltage-Vb-c float32 ×2 VR
0x0055 (85)holdingMax.-Voltage-Vc-a float32 ×2 VR
0x0057 (87)holdingMaximum-Current-a float32 ×2 AR
0x0059 (89)holdingMaximum-Current-b float32 ×2 AR
0x005B (91)holdingMaximum-Current-c float32 ×2 AR
0x005D (93)holdingMaximum-Apparent-Power-a float32 ×2 VR
0x005F (95)holdingMaximum-Apparent-Power-b float32 ×2 VR
0x0061 (97)holdingMaximum-Apparent-Power-c float32 ×2 VR
0x0063 (99)holdingMaximum-Active-Power-a float32 ×2 WR
Calculations run locally in your browser. No data is sent to our servers.
open/gtb · MIT · hosted in France
visitors github roadmap messages contact
SYS OK 15/18 tools online uptime — Rack temp 21.3 °C