Sizing

gtbv3v

Three-Way Valve Sizing

V3V sizing — Cv, authority, network ΔP.

  • kvs
  • authority
  • δp
Thermal load
Fluid
Hydraulics
Valve — optional

Catalogue Kvs · R5 series

6.3m³/h

DN 20 to DN 32

Authority a

0.7

Optimal

Authority 0.70 in [0.50 ; 0.70]: target range.

Nominal Q : 4.299 m³/h

Details

Required theoretical Kv
9.61 m³/h
Actual ΔPv
46.56 kPa · 0.466 bar

Neighbouring alternatives

KvsΔPvAuthorityVerdict
4115.5 kPa0.85Acceptable
1018.5 kPa0.48Borderline
Calculation assumptions
fluid cp
4,186 J/(kg·K)
fluid ρ
1,000 kg/m³
cp·ρ / 3.6e6
1.163 kWh/(m³·K)
Formula
Q [m³/h] = P [kW] / (1.163 · ΔT [K])
Reference
EN 60534-2-1 — turbulent, non-cavitating flow, ρ₀ = 1000 kg/m³.