instrument-ddsu666-h

Autre RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x000F (15)holdingSerial-number string R
0x0047 (71)holdingNumber-of-strings uint16 R
0x0049 (73)holdingRated-power uint32 ×2 kWR
0x004B (75)holdingMaximum-active-power uint32 ×2 kWR
0x004D (77)holdingMaximum-apparent-power uint32 ×2 kVAR
0x004F (79)holdingMaximum-reactive-power-to-grid int32 ×2 kVarR
0x0051 (81)holdingMaximum-reactive-power-from-grid int32 ×2 kVarR
0x07D0 (2000)holdingStatus-1 uint16 R
0x07D2 (2002)holdingStatus-2 uint16 R
0x07D3 (2003)holdingStatus-3 uint32 ×2 R
0x07D8 (2008)holdingAlarm-1 uint16 R
0x07D9 (2009)holdingAlarm-2 uint16 R
0x07DA (2010)holdingAlarm-3 uint16 R
0x07E0 (2016)holdingPVn-voltage int16 VR
0x07E1 (2017)holdingPVn-current int16 AR
0x0810 (2064)holdingInput-power int32 ×2 kWR
0x0812 (2066)holdingLine-voltage-A-B uint16 VR
0x0813 (2067)holdingLine-voltage-B-C uint16 VR
0x0814 (2068)holdingLine-voltage-C-A uint16 VR
0x0815 (2069)holdingPhase-voltage-A uint16 VR
0x0816 (2070)holdingPhase-voltage-B uint16 VR
0x0817 (2071)holdingPhase-voltage-C uint16 VR
0x0818 (2072)holdingPhase-current-A int32 ×2 AR
0x081A (2074)holdingPhase-current-B int32 ×2 AR
0x081C (2076)holdingPhase-current-C int32 ×2 AR
0x081E (2078)holdingPeak-power int32 ×2 kWR
0x0820 (2080)holdingActive-power int32 ×2 kWR
0x0822 (2082)holdingReactive-power int32 ×2 kVarR
0x0824 (2084)holdingPower-factor int16 R
0x0825 (2085)holdingGrid-frequency uint16 HzR
0x0826 (2086)holdingEfficiency uint16 %R
0x0827 (2087)holdingInternal-temperature int16 DCR
0x0828 (2088)holdingInsulation-resistance uint16 MOhmR
0x0829 (2089)holdingDevice-status uint16 R
0x082A (2090)holdingFault-code uint16 R
0x082B (2091)holdingStartup-time uint32 ×2 sR
0x082D (2093)holdingShutdown-time uint32 ×2 sR
0x083A (2106)holdingAccumulated-energy-yield uint32 ×2 kWhR
0x083E (2110)holdingSome-time-1 uint32 ×2 sR
0x0842 (2114)holdingDaily-energy-yield uint32 ×2 kWhR
0x086C (2156)holdingSome-time-2 uint32 ×2 sR
0x0870 (2160)holdingSome-time-3 uint32 ×2 sR
0x13F9 (5113)holdingSome-time-4 uint32 ×2 sR
0x1BBC (7100)holdingMeter-status uint16 R
0x1BC9 (7113)holdingActive-grid-power int32 ×2 WR
0x1BCB (7115)holdingActive-grid-reactive-power int32 ×2 VARR
0x1BD5 (7125)holdingMeter-type uint16 R
0x1BE2 (7138)holdingMeter-detection-result uint16 R
0x2710 (10000)holdingCurrent-time uint32 ×2 sR
0x2904 (10500)holdingSome-time-5 uint32 ×2 sR

Source

upstream : jibrilsharafi · fba9d46

doc d'origine