Briques techniques
gtbmodbus
Catalogue Modbus
Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.
- rtu
- tcp
- registres
circutor
cvm144
Compteur électrique RTU 50 registres À vérifier
À vérifier
- Source upstream : tuto tiers, vérifier les registres
- Pas de config RTU/TCP fournie en amont
- Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet
Registres (50/50)
| scale | unité | ||||||
|---|---|---|---|---|---|---|---|
| 0x0002 (2) | holding | Current---A1 | uint32 ×2 | R | |||
| 0x0004 (4) | holding | Active-power---kW1 | uint32 ×2 | R | |||
| 0x0006 (6) | holding | Reactive-power---kvar1 | uint32 ×2 | R | |||
| 0x0008 (8) | holding | Power-factor---PF1 | uint32 ×2 | PF | R | ||
| 0x000A (10) | holding | Phase-voltage---V2 | uint32 ×2 | V | R | ||
| 0x000C (12) | holding | Current---A2 | uint32 ×2 | R | |||
| 0x000E (14) | holding | Active-power---kW2 | uint32 ×2 | R | |||
| 0x0010 (16) | holding | Reactive-power---kvar2 | uint32 ×2 | R | |||
| 0x0012 (18) | holding | Power-factor---PF2 | uint32 ×2 | PF | R | ||
| 0x0014 (20) | holding | Phase-voltage---V3 | uint32 ×2 | V | R | ||
| 0x0016 (22) | holding | Current---A3 | uint32 ×2 | R | |||
| 0x0018 (24) | holding | Active-power---kW3 | uint32 ×2 | R | |||
| 0x001A (26) | holding | Reactive-power---kvar3 | uint32 ×2 | R | |||
| 0x001C (28) | holding | Power-factor---PF3 | uint32 ×2 | PF | R | ||
| 0x001E (30) | holding | Three-phase-active-power-kWIII | uint32 ×2 | R | |||
| 0x0020 (32) | holding | Three-phase-inductive-power-kvarL-III | uint32 ×2 | R | |||
| 0x0022 (34) | holding | Three-phase-capacitive-power-kvarC-III | uint32 ×2 | R | |||
| 0x0024 (36) | holding | Cos-M-III | uint32 ×2 | R | |||
| 0x0026 (38) | holding | Three-phase-power-factor---PF-III | uint32 ×2 | R | |||
| 0x0028 (40) | holding | Frequency-(L1)---hz | uint32 ×2 | Hz | R | ||
| 0x002A (42) | holding | Line-voltage-L1-L2---v12 | uint32 ×2 | V | R | ||
| 0x002C (44) | holding | Line-voltage-L2-L3---v23 | uint32 ×2 | V | R | ||
| 0x002E (46) | holding | Line-voltage-L3-L1---v31 | uint32 ×2 | V | R | ||
| 0x0030 (48) | holding | %THD-V1 | uint32 ×2 | % | R | ||
| 0x0032 (50) | holding | %THD-V2 | uint32 ×2 | % | R | ||
| 0x0034 (52) | holding | %THD-V3 | uint32 ×2 | % | R | ||
| 0x0036 (54) | holding | %THD-I1 | uint32 ×2 | % | R | ||
| 0x0038 (56) | holding | %THD-I2 | uint32 ×2 | % | R | ||
| 0x003A (58) | holding | %THD-I3 | uint32 ×2 | % | R | ||
| 0x003C (60) | holding | Active-energy---kWh | uint32 ×2 | R | |||
| 0x003E (62) | holding | Inductive-reactive-energy---kvarh-L | uint32 ×2 | R | |||
| 0x0040 (64) | holding | Capacitive-reactive-energy---kvarh-C | uint32 ×2 | R | |||
| 0x0042 (66) | holding | Three-phase-apparent-power | uint32 ×2 | R | |||
| 0x0044 (68) | holding | Power-demand-(L1) | uint32 ×2 | R | |||
| 0x0046 (70) | holding | Three-phase-current | uint32 ×2 | R | |||
| 0x0048 (72) | holding | Neutral-current | uint32 ×2 | R | |||
| 0x004A (74) | holding | Analog-input-1 | uint32 ×2 | R | |||
| 0x004C (76) | holding | Analog-input-2 | uint32 ×2 | R | |||
| 0x004E (78) | holding | Analog-input-3 | uint32 ×2 | R | |||
| 0x0050 (80) | holding | Residual-(earth-leakage)-current | uint32 ×2 | R | |||
| 0x0052 (82) | holding | Power-demand-(L2) | uint32 ×2 | R | |||
| 0x0054 (84) | holding | Power-demand-(L3) | uint32 ×2 | R | |||
| 0x01F4 (500) | holding | Fundamental | uint32 ×2 | R | |||
| 0x01F6 (502) | holding | Harmonic-2 | uint32 ×2 | R | |||
| 0x01F8 (504) | holding | Harmonic-3 | uint32 ×2 | R | |||
| 0x01FA (506) | holding | Harmonic-4 | uint32 ×2 | R | |||
| 0x01FC (508) | holding | Harmonic-5 | uint32 ×2 | R | |||
| 0x01FE (510) | holding | Harmonic-6 | uint32 ×2 | R | |||
| 0x0200 (512) | holding | Harmonic-7 | uint32 ×2 | R | |||
| 0x0202 (514) | holding | Harmonic-8 | uint32 ×2 | R |