Briques techniques

gtbmodbus

Catalogue Modbus

Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.

  • rtu
  • tcp
  • registres

eastron

x96

Autre RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0002 (2)holdingPhase-2-line-to-neutral-volts float32 ×2 VR
0x0004 (4)holdingPhase-3-line-to-neutral-volts float32 ×2 VR
0x0006 (6)holdingPhase-1-current float32 ×2 AR
0x0008 (8)holdingPhase-2-current float32 ×2 AR
0x000A (10)holdingPhase-3-current float32 ×2 AR
0x000C (12)holdingPhase-1-active-power float32 ×2 WR
0x000E (14)holdingPhase-2-active-power float32 ×2 WR
0x0010 (16)holdingPhase-3-active-power float32 ×2 WR
0x0012 (18)holdingPhase-1-apparent-power float32 ×2 VAR
0x0014 (20)holdingPhase-2-apparent-power float32 ×2 VAR
0x0016 (22)holdingPhase-3-apparent-power float32 ×2 VAR
0x0018 (24)holdingPhase-1-reactive-power float32 ×2 VArR
0x001A (26)holdingPhase-2-reactive-power float32 ×2 VArR
0x001C (28)holdingPhase-3-reactive-power float32 ×2 VArR
0x001E (30)holdingPhase-1-power-factor-(1) float32 ×2 NoneR
0x0020 (32)holdingPhase-2-power-factor-(1) float32 ×2 NoneR
0x0022 (34)holdingPhase-3-power-factor-(1) float32 ×2 NoneR
0x0024 (36)holdingPhase-1-phase-angle float32 ×2 DegreesR
0x0026 (38)holdingPhase-2-phase-angle float32 ×2 DegreesR
0x0028 (40)holdingPhase-3-phase-angle float32 ×2 DegreesR
0x002A (42)holdingAverage-line-to-neutral-volts float32 ×2 VR
0x002E (46)holdingAverage-line-current float32 ×2 AR
0x0030 (48)holdingSum-of-line-currents float32 ×2 AR
0x0034 (52)holdingTotal-systerrt-power float32 ×2 WR
0x0038 (56)holdingTotal-systerrt-volt-arrtps float32 ×2 VAR
0x003C (60)holdingTotal-system-var float32 ×2 VArR
0x003E (62)holdingTotal-systerrt-power-factor-(1) float32 ×2 NoneR
0x0042 (66)holdingTotal-systerrt-phase-angle float32 ×2 DegreesR
0x0046 (70)holdingFrequency-of-supply-voltages float32 ×2 HzR
0x0048 (72)holdingImport-wh-since-last-reset float32 ×2 kWhR
0x004A (74)holdingExport-wh-since-last-reset float32 ×2 kWHR
0x004C (76)holdingImport-varh-since-last-reset float32 ×2 kVArhR
0x004E (78)holdingExport-varh-since-last-reset float32 ×2 kVArhR
0x0050 (80)holdingVah-since-last-reset float32 ×2 kVAhR
0x0052 (82)holdingAh-since-last-reset float32 ×2 AhR
0x0054 (84)holdingTotal-systerrt-power-derrtand-(2) float32 ×2 WR
0x0056 (86)holdingMaxirrturrt-total-systerrt-power-derrtand-(2) float32 ×2 WR
0x0058 (88)holdingImport-active-power-derrtand float32 ×2 WR
0x005A (90)holdingImport-active-power-rrtax.-Derrtand float32 ×2 WR
0x005C (92)holdingExport-active-power-derrtand float32 ×2 WR
0x005E (94)holdingExport-active-power-rrtax.-Derrtand float32 ×2 WR
0x0064 (100)holdingTotal-system-va-demand float32 ×2 VAR
0x0066 (102)holdingMaximum-total-system-va-demand float32 ×2 VAR
0x0068 (104)holdingNeutral-current-demand float32 ×2 OpsR
0x006A (106)holdingMaximum-neutral-current-demand float32 ×2 AlIipSR
0x006C (108)holdingTotal-systerrt-reactive-power-derrtand.-(2) float32 ×2 VArR
0x006E (110)holdingMaxirrturrt-total-systerrt-reactive-power-demand-(2) float32 ×2 VArR
0x00A0 (160)holdingVoltage-phase-sequence-(normal=1-reverse=2 float32 ×2 NoneR
0x00A2 (162)holdingCurrent-phase-sequence-(normal=1-reverse=2 float32 ×2 NoneR
0x00C0 (192)holdingNature-of-the-load-(-resistive-=1-inductive-=2-capacitive-=3 float32 ×2 NoneR

Source

upstream : jibrilsharafi · fba9d46

doc d'origine

Calculs effectués localement dans votre navigateur. Aucune donnée envoyée sur nos serveurs.