Compteur électrique RTU 50 registres À vérifier
À vérifier
- Source upstream : tuto tiers, vérifier les registres
- Pas de config RTU/TCP fournie en amont
- Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet
Registres (50/50)
| scale | unité | ||||||
|---|---|---|---|---|---|---|---|
| 0x0010 (16) | holding | Meter-type | uint16 | bit-mapped | R | ||
| 0x0011 (17) | holding | Firmware-version | string ×4 | R | |||
| 0x0013 (19) | holding | Map-version | uint16 | 0 to 65535 | R | ||
| 0x0014 (20) | holding | Meter-configuration | uint16 | bit-mapped | R | ||
| 0x0015 (21) | holding | Asic-version | uint16 | 0-65535 | R | ||
| 0x0383 (899) | holding | Watts,-3-ph-total | float32 ×2 | Watt | R | ||
| 0x0385 (901) | holding | Vars,-3-ph-total | float32 ×2 | VARs | R | ||
| 0x0387 (903) | holding | Vas,-3-ph-total | float32 ×2 | VAs | R | ||
| 0x03E7 (999) | holding | Voits-A-N | float32 ×2 | voIts | R | ||
| 0x03E9 (1001) | holding | Voits-B-N | float32 ×2 | volts | R | ||
| 0x03EB (1003) | holding | Voits-C-N | float32 ×2 | voIts | R | ||
| 0x03ED (1005) | holding | Voits-A-B | float32 ×2 | volts | R | ||
| 0x03EF (1007) | holding | Voits-B-C | float32 ×2 | volts | R | ||
| 0x03F1 (1009) | holding | Voits-C-A | float32 ×2 | volts | R | ||
| 0x03F3 (1011) | holding | Amps-A | float32 ×2 | amps | R | ||
| 0x03F5 (1013) | holding | Amps-B | float32 ×2 | amps | R | ||
| 0x03F7 (1015) | holding | Amps-C | float32 ×2 | amps | R | ||
| 0x03F9 (1017) | holding | Watts,-3-ph-total | float32 ×2 | watts | R | ||
| 0x03FB (1019) | holding | Vars,-3-ph-total | float32 ×2 | VARs | R | ||
| 0x03FD (1021) | holding | Vas,-3-ph-total | float32 ×2 | VAs | R | ||
| 0x0401 (1025) | holding | Frequency | float32 ×2 | Hz | R | ||
| 0x0403 (1027) | holding | Neutral-current | float32 ×2 | amps | R | ||
| 0x044B (1099) | holding | W-hours,-received | int32 ×2 | Wh | R | ||
| 0x044D (1101) | holding | W-hours,-delivered | int32 ×2 | Wh | R | ||
| 0x044F (1103) | holding | W-hours,-net | int32 ×2 | Wh | R | ||
| 0x0451 (1105) | holding | W-hours,-total | int32 ×2 | Wh | R | ||
| 0x0453 (1107) | holding | Var-hours,-positive | int32 ×2 | VARh | R | ||
| 0x0455 (1109) | holding | Var-hours,-negative | int32 ×2 | VARh | R | ||
| 0x0457 (1111) | holding | Var-hours,-net | int32 ×2 | VARh | R | ||
| 0x0459 (1113) | holding | Var-hours,-total | int32 ×2 | VARh | R | ||
| 0x045B (1115) | holding | Va-hours,-total | int32 ×2 | 0 to 99999999 | R | ||
| 0x07CF (1999) | holding | Amps-a,-average | float32 ×2 | amps | R | ||
| 0x07D1 (2001) | holding | Amps-b,-average | float32 ×2 | amps | R | ||
| 0x07D3 (2003) | holding | Amps-c,-average | float32 ×2 | amps | R | ||
| 0x07D5 (2005) | holding | Positive-watts,-3-ph,-average | float32 ×2 | watts | R | ||
| 0x07D7 (2007) | holding | Positive-vars,-3-ph,-average | float32 ×2 | VARs | R | ||
| 0x07D9 (2009) | holding | Negative-watts,-3-ph,-average | float32 ×2 | watts | R | ||
| 0x07DB (2011) | holding | Negative-vars,-3-ph,-average | float32 ×2 | VARs | R | ||
| 0x07DD (2013) | holding | Vas,-3-ph,-average | float32 ×2 | -9999 M to +9999 M | R | ||
| 0x07DF (2015) | holding | Positive-pf,-3-ph,-average | float32 ×2 | -1.00 to +1.00 | R | ||
| 0x07E1 (2017) | holding | Negative-pf,-3-pf,-average | float32 ×2 | -1.00 to +1.00 | R | ||
| 0x0BB9 (3001) | holding | Volts-B-n,-minimum | float32 ×2 | Volt | R | ||
| 0x0C39 (3129) | holding | Negative-power-factor,-3-ph,-maximum-avg-demand | float32 ×2 | -1.00 to +1.00 | R | ||
| 0x1003 (4099) | holding | Phase-A-current | int16 | -1800 to +1800 | R | ||
| 0x1004 (4100) | holding | Phase-B-current | int16 | -1800 to +1800 | R | ||
| 0x1005 (4101) | holding | Phase-C-current | int16 | -1800 to +1800 | R | ||
| 0x1006 (4102) | holding | Angle,-volts-A-B | int16 | -1800 to +1800 | R | ||
| 0x1007 (4103) | holding | Angle,-volts-B-C | int16 | -1800 to +1800 | R | ||
| 0x1008 (4104) | holding | Angle,-volts-C-A | int16 | -1800 to +1800 | R | ||
| 0x1387 (4999) | holding | Meter-status | uint16 | bit-mapped | R |