fronius

primo-5

Onduleur PV RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x9C85 (40069)holdingAC-Current float32 ×2 AR
0x9C87 (40071)holdingPhase-A-Current float32 ×2 AR
0x9C89 (40073)holdingPhase-B-Current float32 ×2 AR
0x9C8B (40075)holdingPhase-C-Current float32 ×2 AR
0x9C8D (40077)holdingPhase-Voltage-AB float32 ×2 VR
0x9C8F (40079)holdingPhase-Voltage-BC float32 ×2 VR
0x9C91 (40081)holdingPhase-Voltage-CA float32 ×2 VR
0x9C93 (40083)holdingPhase-Voltage-AN float32 ×2 VR
0x9C95 (40085)holdingPhase-Voltage-BN float32 ×2 VR
0x9C97 (40087)holdingPhase-Voltage-CN float32 ×2 VR
0x9C99 (40089)holdingAC-Power float32 ×2 WR
0x9C9B (40091)holdingLine-Frequency float32 ×2 HzR
0x9C9D (40093)holdingAC-Apparent-Power float32 ×2 VAR
0x9C9F (40095)holdingAC-Reactive-Power float32 ×2 varR
0x9CA1 (40097)holdingAC-Power-Factor float32 ×2 PctR
0x9CA3 (40099)holdingAC-Energy float32 ×2 WhR
0x9CA5 (40101)holdingDC-Current float32 ×2 AR
0x9CA7 (40103)holdingDC-Voltage float32 ×2 VR
0x9CA9 (40105)holdingDC-Power float32 ×2 WR
0x9CAB (40107)holdingCabinet-Temperature float32 ×2 CR
0x9CAD (40109)holdingHeat-Sink-Temperature float32 ×2 CR
0x9CAF (40111)holdingTransformer-Temperature float32 ×2 CR
0x9CB1 (40113)holdingOther-Temperature float32 ×2 CR
0x9CB3 (40115)holdingEnumerated-value.--Operating-state uint16 R
0x9CB4 (40116)holdingVendor-specific-operating-state-code uint16 R
0x9CB5 (40117)holdingBitmask-value.-Event-fields uint32 ×2 R
0x9CB7 (40119)holdingReserved-for-future-use uint32 ×2 R
0x9CB9 (40121)holdingVendor-defined-events uint32 ×2 R
0x9CBB (40123)holdingVendor-defined-events uint32 ×2 R
0x9CBD (40125)holdingVendor-defined-events uint32 ×2 R
0x9CBF (40127)holdingVendor-defined-events uint32 ×2 R
0x9CC3 (40131)holdingType-of-DER-device.-Default-value-is-4-to-indicate-PV-device. uint16 R
0x9CC4 (40132)holdingContinuous-power-output-capability-of-the-inverter. uint16 WR
0x9CC5 (40133)holdingScale-factor int16 R
0x9CC6 (40134)holdingContinuous-Volt-Ampere-capability-of-the-inverter. uint16 VAR
0x9CC7 (40135)holdingScale-factor int16 R
0x9CC8 (40136)holdingContinuous-VAR-capability-of-the-inverter-in-quadrant-1. int16 varR
0x9CC9 (40137)holdingContinuous-VAR-capability-of-the-inverter-in-quadrant-2. int16 varR
0x9CCA (40138)holdingContinuous-VAR-capability-of-the-inverter-in-quadrant-3. int16 varR
0x9CCB (40139)holdingContinuous-VAR-capability-of-the-inverter-in-quadrant-4. int16 varR
0x9CCC (40140)holdingScale-factor int16 R
0x9CCD (40141)holdingMaximum-RMS-AC-current-level-capability-of-the-inverter. uint16 AR
0x9CCE (40142)holdingScale-factor int16 R
0x9CCF (40143)holdingMinimum-power-factor-capability-of-the-inverter-in-quadrant-1. int16 cos()R
0x9CD0 (40144)holdingMinimum-power-factor-capability-of-the-inverter-in-quadrant-2. int16 cos()R
0x9CD1 (40145)holdingMinimum-power-factor-capability-of-the-inverter-in-quadrant-3. int16 cos()R
0x9CD2 (40146)holdingMinimum-power-factor-capability-of-the-inverter-in-quadrant-4. int16 cos()R
0x9CD3 (40147)holdingScale-factor int16 R
0x9CD4 (40148)holdingNominal-energy-rating-of-storage-device. uint16 WhR
0x9CD5 (40149)holdingScale-factor int16 R