Growatt

MIN 6000TL-XH

Onduleur PV RTUTCP 77 registres À vérifier

À vérifier

  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (77/77)

scaleunité
0x0000 (0)holdingRemote On/Off uint16 R/W
0x0003 (3)holdingMax output active power uint16 %R/W
0x0009 (9)holdingFirmware version uint32 ×2 R/W
0x000C (12)holdingControl firmware version uint32 ×2 R/W
0x000F (15)holdingLCD language
enum (9)
  • 0 → Italian
  • 1 → English
  • 2 → German
  • 3 → Spanish
  • 4 → French
  • 5 → Chinese
  • 6 → Polish
  • 7 → Portuguese
  • 8 → Hungarian
uint16 R/W
0x0BB8 (3000)holdingInverter Machine Status uint16 R
0x0BB8 (3000)holdingInverter Run Status uint16 R
0x0BB9 (3001)holdingSerial Number uint64 ×4 R/W
0x0BB9 (3001)holdingPV total power uint32 ×2 0.1WattsR
0x0BBB (3003)holdingPV1 voltage uint16 0.1VoltsR
0x0BBC (3004)holdingPV1 input current uint16 0.1AmpsR
0x0BBD (3005)holdingPV1 power uint32 ×2 0.1WattsR
0x0BBF (3007)holdingPV2 voltage uint16 0.1VoltsR
0x0BC0 (3008)holdingPV2 input current uint16 0.1AmpsR
0x0BC1 (3009)holdingPV2 power uint32 ×2 0.1WattsR
0x0BCF (3023)holdingOutput power uint32 ×2 0.1WattsR
0x0BD1 (3025)holdingGrid frequency uint16 0.01HzR
0x0BD2 (3026)holdingGrid voltage uint16 0.1VoltsR
0x0BD3 (3027)holdingGrid output current uint16 0.1AmpsR
0x0BD4 (3028)holdingGrid output watt VA uint32 ×2 0.1VoltAmpsR
0x0BD6 (3030)holdingThree phase grid voltage (2) uint16 0.1VoltsR
0x0BD7 (3031)holdingThree phase grid output current (2) uint16 0.1AmpsR
0x0BD8 (3032)holdingThree phase grid output power (2) uint32 ×2 0.1VoltAmpsR
0x0BDA (3034)holdingThree phase grid voltage (3) uint16 0.1VoltsR
0x0BDB (3035)holdingThree phase grid output current (3) uint16 0.1AmpsR
0x0BDC (3036)holdingDischarge Power Rate (Grid First) uint16 R/W
0x0BDC (3036)holdingThree phase grid output power (3) uint32 ×2 0.1VoltAmpsR
0x0BDD (3037)holdingStop Discharge SOC (Grid First) uint16 %R/W
0x0BDE (3038)holdingThree phase grid voltage (RS) uint16 0.1VoltsR
0x0BDF (3039)holdingThree phase grid voltage (ST) uint16 0.1VoltsR
0x0BE0 (3040)holdingThree phase grid voltage (TR) uint16 0.1VoltsR
0x0BE1 (3041)holdingTotal forward power uint32 ×2 0.1WattsR
0x0BE3 (3043)holdingTotal reverse power uint32 ×2 0.1WattsR
0x0BE5 (3045)holdingTotal load power uint32 ×2 0.1WattsR
0x0BE7 (3047)holdingDischarge Power Rate (Bat First) uint16 R/W
0x0BE7 (3047)holdingWork time total uint32 ×2 0.5SecondsR
0x0BE8 (3048)holdingStop Charge SOC (Bat First) uint16 %R/W
0x0BE9 (3049)holdingAC Charge Enable uint16 R/W
0x0BE9 (3049)holdingToday generate energy uint32 ×2 0.1kWhR
0x0BEB (3051)holdingTotal generate energy uint32 ×2 0.1kWhR
0x0BED (3053)holdingPV Energy total uint32 ×2 0.1kWhR
0x0BEF (3055)holdingPV1Energy today uint32 ×2 0.1kWhR
0x0BF1 (3057)holdingPV1 Energy total uint32 ×2 0.1kWhR
0x0BF3 (3059)holdingPV2Energy today uint32 ×2 0.1kWhR
0x0BF5 (3061)holdingPV2 Energy total uint32 ×2 0.1kWhR
0x0BFB (3067)holdingToday energy to user uint32 ×2 0.1kWhR
0x0BFD (3069)holdingTotal energy to user uint32 ×2 0.1kWhR
0x0BFF (3071)holdingToday energy to grid uint32 ×2 0.1kWhR
0x0C01 (3073)holdingTotal energy to grid uint32 ×2 0.1kWhR
0x0C03 (3075)holdingToday energy of user load uint32 ×2 0.1kWhR
0x0C05 (3077)holdingTotal energy of user load uint32 ×2 0.1kWhR
0x0C0D (3085)holdingCommunicate address uint16 R/W
0x0C0E (3086)holdingDerating Mode uint16 R
0x0C15 (3093)holdingInverter temperature uint16 0.1CelsiusR
0x0C16 (3094)holdingIPM Inverter temperature uint16 0.1CelsiusR
0x0C17 (3095)holdingBoost temperature uint16 0.1CelsiusR
0x0C19 (3097)holdingCommunications board temperature uint16 0.1CelsiusR
0x0C1A (3098)holdingP Bus inside voltage uint16 0.1VoltsR
0x0C1B (3099)holdingN Bus inside voltage uint16 0.1VoltsR
0x0C1C (3100)holdingInverter output Power Factor uint16 R
0x0C1D (3101)holdingReal output power percent uint16 1%R
0x0C1E (3102)holdingOutput Maxpower Limited uint32 ×2 0.1WattsR
0x0C20 (3104)holdingInverter standby flag uint16 R
0x0C21 (3105)holdingFault code uint16 R
0x0C22 (3106)holdingWarning code uint16 R
0x0C35 (3125)holdingToday discharge energy uint32 ×2 0.1kWhR
0x0C37 (3127)holdingTotal discharge energy uint32 ×2 0.1kWhR
0x0C39 (3129)holdingToday charge energy uint32 ×2 0.1kWhR
0x0C3B (3131)holdingTotal charge energy uint32 ×2 0.1kWhR
0x0C48 (3144)holdingWork mode uint16 R
0x0C5F (3167)holdingStorage Fault code uint16 R
0x0C60 (3168)holdingStorage Warning code uint16 R
0x0C61 (3169)holdingBattery voltage uint16 0.01VoltsR
0x0C62 (3170)holdingBattery current uint16 0.1AmpsR
0x0C63 (3171)holdingSoC uint16 %R
0x0C6A (3178)holdingDischarge power uint32 ×2 0.1WattsR
0x0C6C (3180)holdingCharge power uint32 ×2 0.1WattsR