Briques techniques
gtbmodbus
Catalogue Modbus
Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.
- rtu
- tcp
- registres
inepro
metering-pro2
Compteur électrique RTU 50 registres À vérifier
À vérifier
- Source upstream : tuto tiers, vérifier les registres
- Pas de config RTU/TCP fournie en amont
- Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet
Registres (50/50)
| scale | unité | ||||||
|---|---|---|---|---|---|---|---|
| 0x4003 (16387) | holding | Modbus-ID | int16 | R | |||
| 0x4004 (16388) | holding | Baud-rate | int16 | R | |||
| 0x4005 (16389) | holding | Protocol-version | float32 ×2 | R | |||
| 0x4007 (16391) | holding | Software-version | float32 ×2 | R | |||
| 0x4009 (16393) | holding | Hardware-version | float32 ×2 | R | |||
| 0x400B (16395) | holding | Meter-amps | int16 | A | R | ||
| 0x400D (16397) | holding | S0-output-rate | float32 ×2 | imp/kWh | R | ||
| 0x400F (16399) | holding | Combination-code | int16 | R | |||
| 0x4011 (16401) | holding | Parity-setting | int16 | R | |||
| 0x4012 (16402) | holding | Current-direction | string | R | |||
| 0x4013 (16403) | holding | L2-current-direction | string | R | |||
| 0x4014 (16404) | holding | L3-current-direction | string | R | |||
| 0x4015 (16405) | holding | Error-code | int16 | R | |||
| 0x4016 (16406) | holding | Power-down-counter | int16 | R | |||
| 0x4017 (16407) | holding | Present-quadrant | int16 | R | |||
| 0x4018 (16408) | holding | L1-quadrant | int16 | R | |||
| 0x4019 (16409) | holding | L2-quadrant | int16 | R | |||
| 0x401A (16410) | holding | L3-quadrant | int16 | R | |||
| 0x401F (16415) | holding | CT-mode | int16 | A | R | ||
| 0x5000 (20480) | holding | Voltage | float32 ×2 | V | R | ||
| 0x5002 (20482) | holding | L1-voltage | float32 ×2 | V | R | ||
| 0x5004 (20484) | holding | L2-voltage | float32 ×2 | V | R | ||
| 0x5006 (20486) | holding | L3-voltage | float32 ×2 | V | R | ||
| 0x5008 (20488) | holding | Grid-frequency | float32 ×2 | Hz | R | ||
| 0x500A (20490) | holding | Current | float32 ×2 | A | R | ||
| 0x500C (20492) | holding | L1-current | float32 ×2 | A | R | ||
| 0x500E (20494) | holding | L2-current | float32 ×2 | A | R | ||
| 0x5010 (20496) | holding | L3-current | float32 ×2 | A | R | ||
| 0x5012 (20498) | holding | Total-active-power | float32 ×2 | kW | R | ||
| 0x5014 (20500) | holding | L1-active-power | float32 ×2 | kW | R | ||
| 0x5016 (20502) | holding | L2-active-power | float32 ×2 | kW | R | ||
| 0x5018 (20504) | holding | L3-active-power | float32 ×2 | kW | R | ||
| 0x501A (20506) | holding | Total-reactive-power | float32 ×2 | kvar | R | ||
| 0x501C (20508) | holding | L1-reactive-power | float32 ×2 | kvar | R | ||
| 0x501E (20510) | holding | L2-reactive-power | float32 ×2 | kvar | R | ||
| 0x5020 (20512) | holding | L3-reactive-power | float32 ×2 | kvar | R | ||
| 0x5022 (20514) | holding | Total-apparent-power | float32 ×2 | kVA | R | ||
| 0x5024 (20516) | holding | L1-apparent-power | float32 ×2 | kVA | R | ||
| 0x5026 (20518) | holding | L2-apparent-power | float32 ×2 | kVA | R | ||
| 0x5028 (20520) | holding | L3-apparent-power | float32 ×2 | kVA | R | ||
| 0x502A (20522) | holding | Power-factor | float32 ×2 | R | |||
| 0x502C (20524) | holding | L1-power-factor | float32 ×2 | R | |||
| 0x502E (20526) | holding | L2-power-factor | float32 ×2 | R | |||
| 0x5030 (20528) | holding | L3-power-factor | float32 ×2 | R | |||
| 0x6000 (24576) | holding | Total-active-energy | float32 ×2 | kWh | R | ||
| 0x6002 (24578) | holding | T1-total-active-energy | float32 ×2 | kWh | R | ||
| 0x6004 (24580) | holding | T2-total-active-energy | float32 ×2 | kWh | R | ||
| 0x6006 (24582) | holding | L1-total-active-energy | float32 ×2 | kWh | R | ||
| 0x6008 (24584) | holding | L2-total-active-energy | float32 ×2 | kWh | R | ||
| 0x600A (24586) | holding | L3-total-active-energy | float32 ×2 | kWh | R |