Briques techniques
gtbmodbus
Catalogue Modbus
Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.
- rtu
- tcp
- registres
kohler
mpac-1000
Autre RTU 50 registres À vérifier
À vérifier
- Source upstream : tuto tiers, vérifier les registres
- Pas de config RTU/TCP fournie en amont
Registres (50/50)
| scale | unité | ||||||
|---|---|---|---|---|---|---|---|
| 0x0001 (1) | holding | Sourcea-line-neutral-L1-l0 | uint16 | Volts AC | R | ||
| 0x0002 (2) | holding | Sourcea-line-neutral-L2-l0 | uint16 | Volts AC | R | ||
| 0x0003 (3) | holding | Sourcea-line-neutral-L3-l0 | uint16 | Volts AC | R | ||
| 0x0004 (4) | holding | Sourceb-line-neutral-L1-l0 | uint16 | Volts AC | R | ||
| 0x0005 (5) | holding | Sourceb-line-neutral-L2-l0 | uint16 | Volts AC | R | ||
| 0x0006 (6) | holding | Sourceb-line-neutral-L3-l0 | uint16 | Volts AC | R | ||
| 0x0007 (7) | holding | Sourcea-line-voltage-L1-L2 | uint16 | Volts AC | R | ||
| 0x0008 (8) | holding | Sourcea-line-voltage-L2-L3 | uint16 | Volts AC | R | ||
| 0x0009 (9) | holding | Sourcea-line-voltage-L3-L1 | uint16 | Volts AC | R | ||
| 0x000A (10) | holding | Sourceb-line-voltage-L1-L2 | uint16 | Volts AC | R | ||
| 0x000B (11) | holding | Sourceb-line-voltage-L2-L3 | uint16 | Volts AC | R | ||
| 0x000C (12) | holding | Sourceb-line-voltage-L3-L1 | uint16 | Volts AC | R | ||
| 0x000D (13) | holding | Sourcea-frequency | uint16 | Hz | R | ||
| 0x000E (14) | holding | Sourceb-frequency | uint16 | Hz | R | ||
| 0x0017 (23) | holding | Sourcea-nominal-voltage | uint16 | Volts AC | R | ||
| 0x0018 (24) | holding | Sourceb-nominal-voltage | uint16 | Volts AC | R | ||
| 0x0019 (25) | holding | Sourcea-nominal-frequency | uint16 | Hz | R | ||
| 0x001A (26) | holding | Sourceb-nominal-frequency | uint16 | Hz | R | ||
| 0x001B (27) | holding | Sourcea-number-of-phases | uint16 | 1 or 3 | R | ||
| 0x001C (28) | holding | Sourceb-number-of-phases | uint16 | 1 or 3 | R | ||
| 0x001D (29) | holding | Rated-amperage | uint16 | 0-4000 | R | ||
| 0x001F (31) | holding | Sourcea-engine-start-time-delay-(id-0x0001) | uint16 | 0-6 sec | R | ||
| 0x0020 (32) | holding | Sourceb-engine-start-time-delay-(id-0x0002) | uint16 | 0-6 sec | R | ||
| 0x0021 (33) | holding | Sourcea-ext-engine-start-time-delay-(id-0x0003) | uint16 | 0-5999 sec | R | ||
| 0x0022 (34) | holding | Sourceb-ext-engine-start-time-delay-(id-0x0004) | uint16 | 0-5999 sec | R | ||
| 0x0023 (35) | holding | Sourcea-engine-cooldown-time-delay-(id-0x0005) | uint16 | 0-5999 sec | R | ||
| 0x0024 (36) | holding | Sourceb-engine-cooldown-time-delay-(id-0x0006) | uint16 | 0-5999 sec | R | ||
| 0x0025 (37) | holding | Preferred-to-standby-time-delay-(id-0x0007) | uint16 | 0-5999 sec | R | ||
| 0x0026 (38) | holding | Standby-to-preferred-time-delay-(id-0x0008) | uint16 | 0-5999 sec | R | ||
| 0x0027 (39) | holding | Off-to-preferred-time-delay-(id-0x0009) | uint16 | 0-5999.9 sec | R | ||
| 0x0028 (40) | holding | Off-to-standby-time-delay-(id-0x000a) | uint16 | 0-5999.9 sec | R | ||
| 0x0029 (41) | holding | Acquire-standby-source-(id-0x000b) | uint16 | 1-5999 sec | R | ||
| 0x002A (42) | holding | Inphase-monitor-synch-(id-0x000c) | uint16 | 1-5999 sec | R | ||
| 0x002C (44) | holding | Sourcea-over-volt-dropout-trip-point | uint16 | 105 - 135) % of rated source voltage | R | ||
| 0x002D (45) | holding | Sourcea-over-volt-pickup-trip-point | uint16 | 95 - 100)% of over voltage dropout point | R | ||
| 0x002E (46) | holding | Sourcea-under-volt-pickup-trip-point | uint16 | 85 - 100) % of rated source voltage | R | ||
| 0x002F (47) | holding | Sourcea-under-volt-dropout-trip-point | uint16 | 75 - 98) % of overvoltage pickup point | R | ||
| 0x0030 (48) | holding | Sourcea-voltage-debounce-time | uint16 | Sec | R | ||
| 0x0031 (49) | holding | Sourceb-over-volt-dropout-trip-point | uint16 | 105 - 135) % of rated source voltage | R | ||
| 0x0032 (50) | holding | Sourceb-over-volt-pickup-trip-point | uint16 | 95 - 100)% of over voltage dropout point | R | ||
| 0x0033 (51) | holding | Sourceb-under-volt-pickup-trip-point | uint16 | 85 - 100) % of rated source voltage | R | ||
| 0x0034 (52) | holding | Sourceb-under-volt-dropout-trip-point | uint16 | 75 - 98) % of overvoltage pickup point | R | ||
| 0x0035 (53) | holding | Sourceb-voltage-debounce-time | uint16 | Sec | R | ||
| 0x0036 (54) | holding | Sourcea-over-freq-dropout-trip-point | uint16 | 101 -105) % of overfreq pickup point | R | ||
| 0x0037 (55) | holding | Sourcea-over-freq-pickup-trip-point | uint16 | 105 - 120) % of rated source freq | R | ||
| 0x0038 (56) | holding | Sourcea-under-freq-dropout-trip-point | uint16 | 95 - 99) % of underfreq pickup point | R | ||
| 0x0039 (57) | holding | Sourcea-under-freq-pickup-trip-point | uint16 | 80 - 95)% of rated system frequency | R | ||
| 0x003A (58) | holding | Sourcea-freq-dropout-time | uint16 | Sec | R | ||
| 0x003B (59) | holding | Sourceb-over-freq-dropout-trip-point | uint16 | 101 -105) % of overfreq pickup point | R | ||
| 0x003C (60) | holding | Sourceb-over-freq-pickup-trip-point | uint16 | 105 - 120) % of rated source freq | R |