Briques techniques
gtbmodbus
Catalogue Modbus
Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.
- rtu
- tcp
- registres
Meltem
meltem_default
VMC / CTA RTUTCP 19 registres À vérifier
À vérifier
- Source : ioBroker/modbus-templates. Vérifier l'ordre des octets et le sens du facteur sur datasheet.
Registres (19/19)
| scale | unité | ||||||
|---|---|---|---|---|---|---|---|
| 0xA028 (41000) | holding | Extract air temperature · 2 | uint16 | 2 | Extract air temperature | R/W | |
| 0xA02A (41002) | holding | Outdoor air temperature · 2 | uint16 | 2 | Outdoor air temperature | R/W | |
| 0xA02C (41004) | holding | Exhaust air temperature · 2 | uint16 | 2 | Exhaust air temperature | R/W | |
| 0xA031 (41009) | holding | Supply air temperature · 2 | uint16 | 2 | Supply air temperature | R/W | |
| 0xA038 (41016) | holding | Error message · 2 | uint16 | Error message: 0 = device OK; 1 = error | R/W | ||
| 0xA039 (41017) | holding | Air filter change indicator · 2 | uint16 | Air filter change indicator: 0 = time not elapsed; 1 = elapsed | R/W | ||
| 0xA03A (41018) | holding | Frost protection function · 2 | uint16 | Frost protection function: 0 = not active; 1 = active | R/W | ||
| 0xA03C (41020) | holding | Ventilation level extract air · 2 | uint16 | Ventilation level for extract air | R/W | ||
| 0xA03D (41021) | holding | Ventilation level supply air · 2 | uint16 | Ventilation level for supply air | R/W | ||
| 0xA043 (41027) | holding | Time until air filter change · 2 | uint16 | Time until air filter change | R/W | ||
| 0xA046 (41030) | holding | Ventilation unit operating hours · 2 | uint16 | Ventilation unit operating hours | R/W | ||
| 0xA048 (41032) | holding | Fan motors operating hours · 2 | uint16 | Fan motors operating hours | R/W | ||
| 0xA08C (41100) | holding | Mode · 2 | uint16 | R/W | |||
| 0xA08D (41101) | holding | Mode Zuluft · 2 | uint16 | R/W | |||
| 0xA08E (41102) | holding | Mode Abluft · 2 | uint16 | R/W | |||
| 0xA0A0 (41120) | holding | setModeType · 2 | uint16 | 1: Off, 2: Automatic Modes, 3: Balanced Ventilation Level, 4: Unbalanced Ventilation Level | R | ||
| 0xA0A1 (41121) | holding | setModeSubType · 2 | uint16 | Automatic Modes: 112=Humidity control (F & FC units), 144=CO2 control (FC unit), 16=Automatic mode (FC unit); Balanced ventilation level: 0-200 (=0-100m³ on both fans); Unbalanced Ventilation Level: 0-200 (=0-100m³ on supply air fan) | R | ||
| 0xA0A2 (41122) | holding | setModeExhaustFan · 2 | uint16 | Only for Unbalanced Ventilation Level: 0-200 (=0-100m³ on exhaust air fan) | R | ||
| 0xA0AC (41132) | holding | setModeConfirmWrite · 2 | uint16 | Registers 41120, 41121 (and 41122 for unbalanced ventilation) and 41132 must be written in succession. Register 41132 must always be written last | R |
Source
upstream : iobroker · 6b2b335