mikro

dpm680

Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0003 (3)holdingDevice-type-sub uint16 x0000R
0x0004 (4)holdingVersion-number-main uint16 x0000 ; 0x0002R
0x0006 (6)holdingVersion-number-sub uint16 x0000 ; 0x0000R
0x03E9 (1001)holdingParity-selection uint16 =none, 1 stop bit 1=none, 2 stop bit 2=odd, 1 stop bit 3=even, 1 stop bitR
0x03EA (1002)holdingBaudrate-selection uint16 =300 2=600 3=1200 4=2400 5=4800 6=9600 7=19200 8=38400R
0x03EB (1003)holdingIp-address uint16 x00 | 0x00 ; 0x00 | 0x00R
0x03ED (1005)holdingSubnet-mask uint16 x00 | 0x00 ; 0x00 | 0x00R
0x0FA0 (4000)holdingReal-energy int64 ×4 WhR
0x0FA4 (4004)holdingApparent-energy int64 ×4 VAhR
0x0FA8 (4008)holdingReactive-energy int64 ×4 VArhR
0x0FAC (4012)holdingTotal-real-power int32 ×2 WR
0x0FAE (4014)holdingTotal-apparent-power int32 ×2 VAR
0x0FB0 (4016)holdingTotal-reactive-power int32 ×2 VArR
0x0FB2 (4018)holdingTotal-power-factor uint16 1R
0x0FB3 (4019)holdingFrequency uint16 HzR
0x0FB4 (4020)holdingInstantaneous-current-A uint32 ×2 AR
0x0FB6 (4022)holdingInstantaneous-current-B uint32 ×2 AR
0x0FB8 (4024)holdingInstantaneous-current-C uint32 ×2 AR
0x0FBA (4026)holdingInstantaneous-current-N uint32 ×2 AR
0x0FBC (4028)holdingVoltage-line-ab uint32 ×2 VR
0x0FBE (4030)holdingVoltage-line-bc uint32 ×2 VR
0x0FC0 (4032)holdingVoltage-line-ac uint32 ×2 VR
0x0FC2 (4034)holdingVoltage-phase-an uint32 ×2 VR
0x0FC4 (4036)holdingVoltage-phase-bn uint32 ×2 VR
0x0FC6 (4038)holdingVoltage-phase-cn uint32 ×2 VR
0x0FC8 (4040)holdingReal-power-A int32 ×2 WR
0x0FCA (4042)holdingReal-power-B int32 ×2 WR
0x0FCC (4044)holdingReal-power-C int32 ×2 WR
0x0FCE (4046)holdingApparent-power-A int32 ×2 VAR
0x0FD0 (4048)holdingApparent-power-B int32 ×2 VAR
0x0FD2 (4050)holdingApparent-power-C int32 ×2 VAR
0x0FD4 (4052)holdingReactive-power-A int32 ×2 VArR
0x0FD6 (4054)holdingReactive-power-B int32 ×2 VArR
0x0FD8 (4056)holdingReactive-power-C int32 ×2 VArR
0x0FDA (4058)holdingCurrent-demand-A uint32 ×2 ArmsR
0x0FDC (4060)holdingCurrent-demand-B uint32 ×2 ArmsR
0x0FDE (4062)holdingCurrent-demand-C uint32 ×2 ArmsR
0x0FE0 (4064)holdingReal-power-demand int32 ×2 WR
0x0FE2 (4066)holdingReactive-power-demand int32 ×2 VArR
0x0FE4 (4068)holdingApparent-power-demand int32 ×2 VAR
0x0FE6 (4070)holdingPositive-sequence-current uint32 ×2 AR
0x0FE8 (4072)holdingNegative-sequence-current uint32 ×2 AR
0x0FEA (4074)holdingZero-sequence-current uint32 ×2 AR
0x0FEC (4076)holdingPositive-sequence-phase-voltage uint32 ×2 VR
0x0FEE (4078)holdingNegative-sequence-phase-voltage uint32 ×2 VR
0x0FF0 (4080)holdingZero-sequence-phase-voltage uint32 ×2 VR
0x0FF2 (4082)holdingCurrent-thd-A uint16 %R
0x0FF3 (4083)holdingCurrent-thd-B uint16 %R
0x0FF4 (4084)holdingCurrent-thd-C uint16 %R
0x0FF5 (4085)holdingVoltage-thd-A uint16 %R