Briques techniques
gtbmodbus
Catalogue Modbus
Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.
- rtu
- tcp
- registres
rayleigh
instruments-ri-f100
Compteur électrique RTU 50 registres À vérifier
À vérifier
- Source upstream : tuto tiers, vérifier les registres
- Pas de config RTU/TCP fournie en amont
- Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet
Registres (50/50)
| scale | unité | ||||||
|---|---|---|---|---|---|---|---|
| 0x0001 (1) | holding | Voltage-v2n | float32 ×2 | R | |||
| 0x0003 (3) | holding | Voltage-v3n | float32 ×2 | R | |||
| 0x0005 (5) | holding | Average-voltage-ln | float32 ×2 | R | |||
| 0x0007 (7) | holding | Voltage-V12 | float32 ×2 | R | |||
| 0x0009 (9) | holding | Voltage-V23 | float32 ×2 | R | |||
| 0x000B (11) | holding | Voltage-V31 | float32 ×2 | R | |||
| 0x000D (13) | holding | Average-voltage-ll | float32 ×2 | R | |||
| 0x000F (15) | holding | Current-I1 | float32 ×2 | R | |||
| 0x0011 (17) | holding | Current-I2 | float32 ×2 | R | |||
| 0x0013 (19) | holding | Current-I3 | float32 ×2 | R | |||
| 0x0015 (21) | holding | Average-current | float32 ×2 | R | |||
| 0x0017 (23) | holding | kW1 | float32 ×2 | R | |||
| 0x0019 (25) | holding | kW2 | float32 ×2 | R | |||
| 0x001B (27) | holding | kW3 | float32 ×2 | R | |||
| 0x001D (29) | holding | Kva1 | float32 ×2 | R | |||
| 0x001F (31) | holding | Kva2 | float32 ×2 | R | |||
| 0x0021 (33) | holding | Kva3 | float32 ×2 | R | |||
| 0x0023 (35) | holding | Kvar1 | float32 ×2 | R | |||
| 0x0025 (37) | holding | Kvar2 | float32 ×2 | R | |||
| 0x0027 (39) | holding | Kvar3 | float32 ×2 | R | |||
| 0x0029 (41) | holding | Total-kw | float32 ×2 | R | |||
| 0x002B (43) | holding | Total-kva | float32 ×2 | KVA | R | ||
| 0x002D (45) | holding | Total-kvar | float32 ×2 | KVAr | R | ||
| 0x002F (47) | holding | PF1 | float32 ×2 | R | |||
| 0x0031 (49) | holding | PF2 | float32 ×2 | R | |||
| 0x0033 (51) | holding | PF3 | float32 ×2 | R | |||
| 0x0035 (53) | holding | Average-pf | float32 ×2 | R | |||
| 0x0037 (55) | holding | Frequency | float32 ×2 | R | |||
| 0x0039 (57) | holding | Total-net-kwh | float32 ×2 | kWh | R | ||
| 0x003B (59) | holding | Total-net-kvah | float32 ×2 | R | |||
| 0x003D (61) | holding | Total-net-kvarh | float32 ×2 | kVArh | R | ||
| 0x003F (63) | holding | Kw-max-active-power | float32 ×2 | R | |||
| 0x0041 (65) | holding | Kw-min-active-power | float32 ×2 | R | |||
| 0x0043 (67) | holding | Kvar-max-reactive-power | float32 ×2 | R | |||
| 0x0045 (69) | holding | Kvar-min-reactive-power | float32 ×2 | R | |||
| 0x0047 (71) | holding | Kva-max-apparent-power | float32 ×2 | R | |||
| 0x0049 (73) | holding | Max-I1-demand | float32 ×2 | R | |||
| 0x004B (75) | holding | Max-I2-demand | float32 ×2 | R | |||
| 0x004D (77) | holding | Max-I3-demand | float32 ×2 | R | |||
| 0x004F (79) | holding | Max-avg-demand | float32 ×2 | R | |||
| 0x0051 (81) | holding | Run-hour | float32 ×2 | R | |||
| 0x0053 (83) | holding | Kwh1-(imp) | float32 ×2 | R | |||
| 0x0055 (85) | holding | Kwh2-(imp) | float32 ×2 | R | |||
| 0x0057 (87) | holding | Kwh3-(imp) | float32 ×2 | R | |||
| 0x0059 (89) | holding | Kwh1-(exp) | float32 ×2 | R | |||
| 0x005B (91) | holding | Kwh2-(exp) | float32 ×2 | R | |||
| 0x005D (93) | holding | Kwh3-(exp) | float32 ×2 | R | |||
| 0x005F (95) | holding | Total-kwh-(imp) | float32 ×2 | kWh | R | ||
| 0x0061 (97) | holding | Total-kwh-(exp) | float32 ×2 | kWh | R | ||
| 0x0063 (99) | holding | Kvarh1-(imp) | float32 ×2 | R |