schneider

electric-em3502-em3550

Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0002 (2)holdingTotal-instantaneous-real-power-(3-phase-total) uint16 kWR
0x0003 (3)holdingTotal-instantaneous-reactive-power-(3-phase-total) uint16 kVARR
0x0004 (4)holdingTotal-instantaneous-apparent-power-(3-phase-total) uint16 kVAR
0x0005 (5)holdingTotal-power-factor-(total-kw-/-total-kva) uint16 RatioR
0x0006 (6)holdingVoltage,-L-l,-average-of-3-phases uint16 VoltR
0x0007 (7)holdingVoltage,-L-n,-average-of-3-phases uint16 VoltR
0x0008 (8)holdingCurrent,-average-of-3-phases uint16 AmpR
0x0009 (9)holdingReal-power,-phase-A uint16 kWR
0x000A (10)holdingReal-power,-phase-B uint16 kWR
0x000B (11)holdingReal-power,-phase-C uint16 kWR
0x000C (12)holdingPower-factor,-phase-A uint16 RatioR
0x000D (13)holdingPower-factor,-phase-B uint16 RatioR
0x000E (14)holdingPower-factor,-phase-C uint16 RatioR
0x000F (15)holdingVoltage,-phase-A-B uint16 VoltR
0x0010 (16)holdingVoltage,-phase-B-C uint16 VoltR
0x0011 (17)holdingVoltage,-phase-A-C uint16 VoltR
0x0012 (18)holdingVoltage,-phase-A-N uint16 VoltR
0x0013 (19)holdingVoltage,-phase-B-N uint16 VoltR
0x0014 (20)holdingVoltage,-phase-C-N uint16 VoltR
0x0015 (21)holdingCurrent,-instantaneous,-phase-A uint16 AmpR
0x0016 (22)holdingCurrent,-instantaneous,-phase-B uint16 AmpR
0x0017 (23)holdingCurrent,-instantaneous,-phase-C uint16 AmpR
0x0019 (25)holdingFrequency-(derived-from-phase-a) uint16 HzR
0x001A (26)holdingApparent-energy-consumption-(msr) uint32 ×2 KVAhR
0x001C (28)holdingReactive-energy-consumption-(msr) uint32 ×2 KVARhR
0x001E (30)holdingApparent-power,-phase-A uint16 kVAR
0x001F (31)holdingApparent-power,-phase-B uint16 kVAR
0x0020 (32)holdingApparent-power,-phase-C uint16 kVAR
0x0021 (33)holdingReactive-power,-phase-A uint16 kVARR
0x0022 (34)holdingReactive-power,-phase-B uint16 kVARR
0x0023 (35)holdingReactive-power,-phase-C uint16 kVARR
0x0024 (36)holdingTotal-real-power-present-demand uint16 kWR
0x0025 (37)holdingTotal-reactive-power-present-demand uint16 kVARR
0x0026 (38)holdingTotal-apparent-power-present-demand uint16 kVAR
0x0027 (39)holdingTotal-real-power-max.-demand uint16 kWR
0x0028 (40)holdingTotal-reactive-power-max.-demand uint16 kVARR
0x0029 (41)holdingTotal-apparent-power-max.-demand uint16 kVAR
0x002A (42)holdingPulse-counter-1-(real-energy) uint32 ×2 R
0x002C (44)holdingPulse-counter-2-(reactive-energy) uint32 ×2 R
0x002E (46)holdingReal-energy-consumption-phase-A uint32 ×2 kWhR
0x0030 (48)holdingReal-energy-consumption-phase-B uint32 ×2 kWhR
0x0032 (50)holdingReal-energy-consumption-phase-C uint32 ×2 kWhR
0x0081 (129)holdingSingle-phase:-A-+-N uint16 R
0x0082 (130)holdingCt-ratio-primary uint16 AmpsR
0x0083 (131)holdingCt-ratio-secondary-interface-(1-or-1/3-v,-may-not-be-user-configurable) uint16 R
0x0084 (132)holdingPt-ratio:-the-meter-scales-this-value-by-100-(i.e.-entering-200-yields-a-potential-transformer-ratio-of-2:1).-the-default-is-100-(1.00:1),-which-is-with-no-pt-attached.-set-this-value-before-setting-the-system-voltage-(below) uint16 R
0x0085 (133)holdingSystem-voltage:-this-voltage-is-line-to-line,-except-for-system-type-10-which-is-line-to-neutral.-the-meter-uses-this-value-to-calculate-the-full-scale-power-for-the-analog-outputs-and-pulse-configuration-(below),-and-as-full-scale-for-phase-loss-(register-142).-the-meter-will-refuse-voltages-that-are-outside-the-range-of-82-660-volts-when-divided-by-the-pt-ratio-(above) uint16 R
0x0086 (134)holdingTheoretical-maximum-system-power:-this-read-only-value-is-the-theoretical-maximum-power-the-meter-can-expect-to-see-on-a-service.-this-value-is-100%-of-scale-on-the-analog-output-(0-5-vdc-or-4-20-ma),-if-equipped.-the-meter-recalculates-this-value-if-the-user-changes-the-ct-size,-system-type,-or-system-voltage.-this-integer-value-has-the-same-scale-as-other-integer-power-registers-(see-register-140-for-power-scaling) uint16 kWR
0x0088 (136)holdingDisplay-units:-0-=-iec-(u,-v,-p,-q,-s),-1-=-ieee-(default:-vll,-vln,-w,-var,-va) uint16 R
0x0089 (137)holdingScale-factors-note:-these-registers-contain-a-signed-integer-that-scales-the-corresponding-integer-registers.-floating-point-registers-are-not-scaled.-scaling-is-recalculated-when-the-meter-configuration-is-changed int16 R