Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0002 (2)holdingTotal-instantaneous-real-power-(3-phase-total) uint16 kWR
0x0003 (3)holdingTotal-instantaneous-reactive-power-(3-phase-total) uint16 kVARR
0x0004 (4)holdingTotal-instantaneous-apparent-power-(3-phase-total) uint16 kVAR
0x0005 (5)holdingTotal-power-factor-(total-kw-/-total-kva) uint16 RatioR
0x0006 (6)holdingVoltage,-line-to-line,-average-of-phases uint16 VoltR
0x0007 (7)holdingVoltage,-line-to-neutral,-average-of-phases uint16 VoltR
0x0008 (8)holdingCurrent,-average-of-phases uint16 AmpR
0x0009 (9)holdingReal-power,-L1 uint16 kWR
0x000A (10)holdingReal-power,-L2 uint16 kWR
0x000B (11)holdingReal-power,-L3 uint16 kWR
0x000C (12)holdingPower-factor,-L1 uint16 RatioR
0x000D (13)holdingPower-factor,-L2 uint16 RatioR
0x000E (14)holdingPower-factor,-L3 uint16 RatioR
0x000F (15)holdingVoltage,-L1-L2 uint16 VoltR
0x0010 (16)holdingVoltage,-L2-L3 uint16 VoltR
0x0011 (17)holdingVoltage,-L3-L1 uint16 VoltR
0x0012 (18)holdingVoltage,-L1-N uint16 VoltR
0x0013 (19)holdingVoltage,-L2-N uint16 VoltR
0x0014 (20)holdingVoltage,-L3-N uint16 VoltR
0x0015 (21)holdingCurrent,-instantaneous,-L1 uint16 AmpR
0x0016 (22)holdingCurrent,-instantaneous,-L2 uint16 AmpR
0x0017 (23)holdingCurrent,-instantaneous,-L3 uint16 AmpR
0x0018 (24)holdingPresent-demand-sub-interval uint16 kWR
0x0019 (25)holdingMinimum-demand uint16 kWR
0x001A (26)holdingMaximum-demand uint16 kWR
0x001B (27)holdingPresent-demand uint16 kWR
0x001C (28)holdingPeak-demand uint16 kWR
0x001E (30)holdingCt-size-(100,-300,-etc.) uint16 AmpsR
0x001F (31)holdingCount-of-kwh-resets uint16 CountR
0x0020 (32)holdingCount-of-peak-demand-resets uint16 CountR
0x0021 (33)holdingCount-of-sub-intervals uint16 CountR
0x0022 (34)holdingCount-of-number-readings-in-present-sub-interval uint16 CountR
0x0023 (35)holdingSystem-type:-see-manual uint16 integerR
0x0024 (36)holdingSub-interval-length:-sets-the-length-of-a-sub-interval.-value-is-the-number-of-seconds-times-5-(for-example,-15-minutes-is-4500).-for-sync-to-comms,-set-this-to-zero uint16 integerR
0x0025 (37)holdingNumber-of-sub-intervals-per-demand-interval.-sets-the-number-of-sub-intervals-that-make-a-single-demand-interval.-legal-values-are-1-to-6.-for-block-demand,-set-this-to-1 uint16 integerR
0x0026 (38)holdingCommand uint16 bit mapR
0x0100 (256)holdingReal-energy-consumption float32 ×2 kWhR
0x0102 (258)holdingReal-energy-consumption-(redundant) float32 ×2 kWhR
0x0104 (260)holdingTotal-instantaneous-real-power float32 ×2 kWR
0x0106 (262)holdingTotal-instantaneous-reactive-power float32 ×2 kVARR
0x0108 (264)holdingTotal-instantaneous-apparent-power float32 ×2 kVAR
0x010A (266)holdingTotal-power-factor-(total-kw-/-total-kva) float32 ×2 RatioR
0x010C (268)holdingVoltage,-line-to-line,-average-of-3-phases float32 ×2 VoltR
0x010E (270)holdingVoltage,-line-to-neutral,-average-of-3-phases float32 ×2 VoltR
0x0110 (272)holdingCurrent,-average-of-3-phases float32 ×2 AmpR
0x0112 (274)holdingReal-power,-L1 float32 ×2 kWR
0x0114 (276)holdingReal-power,-L2 float32 ×2 kWR
0x0116 (278)holdingReal-power,-L3 float32 ×2 kWR
0x0118 (280)holdingPower-factor,-L1 float32 ×2 RatioR
0x011A (282)holdingPower-factor,-L2 float32 ×2 RatioR

Source