Briques techniques

gtbmodbus

Catalogue Modbus

Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.

  • rtu
  • tcp
  • registres

schneider

electric-pm5000-pm5200

Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x001D (29)holdingMeter-name string ×40 R
0x0031 (49)holdingMeter-model string ×40 R
0x0045 (69)holdingManufacturer string ×40 R
0x0059 (89)holdingProduct-ID-number uint16 R
0x0081 (129)holdingSerial-number uint32 ×2 R
0x0087 (135)holdingHardware-revision string ×10 R
0x0723 (1827)holdingNumber-of-metering-system-restarts uint16 R
0x0724 (1828)holdingNumber-of-control-power-failures uint16 R
0x0729 (1833)holdingDuration-of-last-control-power-failure uint32 ×2 secondsR
0x072B (1835)holdingCause-of-last-meter-reset uint16 R
0x072C (1836)holdingYear uint16 yearR
0x072D (1837)holdingMonth uint16 monthR
0x072E (1838)holdingDay uint16 daysR
0x072F (1839)holdingHour uint16 hoursR
0x0730 (1840)holdingMinute uint16 minutesR
0x0731 (1841)holdingSecond uint16 secondsR
0x0732 (1842)holdingMillisecond uint16 msecR
0x0734 (1844)holdingYear uint16 R
0x0735 (1845)holdingMonth-and-day uint16 R
0x0736 (1846)holdingHour-and-minute uint16 R
0x0737 (1847)holdingMilliseconds uint16 R
0x07CF (1999)holdingConditional-energy-control-status uint16 R
0x07D1 (2001)holdingActive-load-timer uint32 ×2 secondsR
0x07D3 (2003)holdingMeter-operation-timer uint32 ×2 secondsR
0x07D5 (2005)holdingCycle-count uint32 ×2 R
0x07DD (2013)holdingNumber-of-phases uint16 R
0x07DE (2014)holdingNumber-of-wires uint16 R
0x07DF (2015)holdingPower-system-configuration uint16 R
0x07E0 (2016)holdingNominal-frequency uint16 HzR
0x07E1 (2017)holdingNominal-voltage float32 ×2 VR
0x07E3 (2019)holdingNominal-current float32 ×2 AR
0x07E5 (2021)holdingNominal-power-factor uint32 ×2 R
0x07E7 (2023)holdingNormal-phase-rotation uint16 R
0x07E8 (2024)holdingNumber-VTs uint16 R
0x07E9 (2025)holdingVT-primary float32 ×2 VR
0x07EB (2027)holdingVT-secondary uint16 VR
0x07EC (2028)holdingNumber-CTs uint16 R
0x07ED (2029)holdingCT-primary uint16 AR
0x07EE (2030)holdingCT-secondary uint16 AR
0x07F1 (2033)holdingCT-location-for-1-or-2-CT-metering uint16 R
0x07F2 (2034)holdingVT-location-for-1-or-2-VT-metering uint16 R
0x07F3 (2035)holdingVT-connection-type uint16 R
0x07FF (2047)holdingPeak-current-demand-over-last-year float32 ×2 AR
0x0801 (2049)holdingActive-load-timer-setpoint float32 ×2 AR
0x084D (2125)holdingAlarm-/-energy-LED-mode uint16 R
0x0851 (2129)holdingEnergy-channel uint16 R
0x0853 (2131)holdingPulse-weight uint32 ×2 kWh, kVAh, kVAhR
0x0855 (2133)holdingEnergy-channel uint16 R
0x0857 (2135)holdingPulse-weight uint32 ×2 kWh, kVAh, kVAhR
0x0859 (2137)holdingEnergy-channel uint16 R

Source

upstream : jibrilsharafi · fba9d46

doc d'origine

Calculs effectués localement dans votre navigateur. Aucune donnée envoyée sur nos serveurs.