Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x001D (29)holdingMeter-name string ×40 R
0x0031 (49)holdingMeter-model string ×40 R
0x0045 (69)holdingManufacturer string ×40 R
0x0059 (89)holdingProduct-ID-number uint16 R
0x0081 (129)holdingSerial-number uint32 ×2 R
0x0087 (135)holdingHardware-revision string ×10 R
0x0664 (1636)holdingPresent-firmware-version-(DLF-format)-X.Y.T uint16 R
0x0665 (1637)holdingX-major uint16 R
0x0666 (1638)holdingY-minor uint16 R
0x0667 (1639)holdingZ-quality uint16 R
0x0669 (1641)holdingPrevious-firmware-version-(DLF-format)-X.Y.T uint16 R
0x066A (1642)holdingX-major uint16 R
0x066B (1643)holdingY-minor uint16 R
0x066C (1644)holdingZ-quality uint16 R
0x0684 (1668)holdingPresent-firmware-version-(DLF-format)-X.Y.T uint16 R
0x06A4 (1700)holdingPresent-firmware-version-(DLF-format)-X.Y.T uint16 R
0x0723 (1827)holdingNumber-of-metering-system-restarts uint16 R
0x0724 (1828)holdingNumber-of-control-power-failures uint16 R
0x0729 (1833)holdingDuration-of-last-control-power-failure uint32 ×2 secondsR
0x072B (1835)holdingCause-of-last-meter-reset uint16 R
0x072C (1836)holdingYear uint16 yearR
0x072D (1837)holdingMonth uint16 monthR
0x072E (1838)holdingDay uint16 daysR
0x072F (1839)holdingHour uint16 hoursR
0x0730 (1840)holdingMinute uint16 minutesR
0x0731 (1841)holdingSecond uint16 secondsR
0x0732 (1842)holdingMillisecond uint16 msecR
0x0734 (1844)holdingYear uint16 R
0x0735 (1845)holdingMonth-and-day uint16 R
0x0736 (1846)holdingHour-and-minute uint16 R
0x0737 (1847)holdingMilliseconds uint16 R
0x077F (1919)holdingRevenue-security-switch-status uint16 R
0x0780 (1920)holdingRevenue-security-status uint16 R
0x07D1 (2001)holdingActive-load-timer uint32 ×2 secondsR
0x07D3 (2003)holdingMeter-operation-timer uint32 ×2 secondsR
0x07DD (2013)holdingNumber-of-phases uint16 R
0x07DE (2014)holdingNumber-of-wires uint16 R
0x07DF (2015)holdingPower-system-configuration uint16 R
0x07E0 (2016)holdingNominal-frequency uint16 HzR
0x07E1 (2017)holdingNominal-voltage float32 ×2 VR
0x07E3 (2019)holdingNominal-current float32 ×2 AR
0x07E7 (2023)holdingNormal-phase-rotation uint16 R
0x07E8 (2024)holdingNumber-VTs uint16 R
0x07E9 (2025)holdingVT-primary float32 ×2 VR
0x07EB (2027)holdingVT-secondary uint16 VR
0x07EC (2028)holdingNumber-CTs uint16 R
0x07ED (2029)holdingCT-primary uint16 AR
0x07EE (2030)holdingCT-secondary uint16 AR
0x07EF (2031)holdingCT-primary-N uint16 AR
0x07F0 (2032)holdingCT-secondary-N uint16 AR