electric-powerlogic-ion6200

Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0002 (2)holdingFirmware-revision uint16 R
0x0003 (3)holdingOem-identification uint16 R
0x0004 (4)holdingMeter-options uint32 ×2 R
0x0006 (6)holding#-meter-power-ups uint16 R
0x0007 (7)holding#-peak-demand-resets uint16 R
0x0008 (8)holdingMeter-on-time uint32 ×2 R
0x000A (10)holding#-flash-erase-cycles uint32 ×2 R
0x000C (12)holdingDevice-type uint16 R
0x000E (14)holdingDemand-interval-down-counter uint16 R
0x0063 (99)holdingVln-a uint16 R
0x0064 (100)holdingVln-b uint16 R
0x0065 (101)holdingVln-c uint16 R
0x0066 (102)holdingVln-avg uint16 R
0x0067 (103)holdingVll-ab uint16 R
0x0068 (104)holdingVll-bc uint16 R
0x0069 (105)holdingVll-ca uint16 R
0x006A (106)holdingVll-avg uint16 R
0x006B (107)holdingI-a uint16 R
0x006C (108)holdingI-b uint16 R
0x006D (109)holdingI-c uint16 R
0x006E (110)holdingI-avg uint16 R
0x006F (111)holdingI-demand uint16 R
0x0070 (112)holdingI-peak-demand uint16 R
0x0071 (113)holdingI4 uint16 R
0x0072 (114)holdingFrequency int16 R
0x0073 (115)holdingPF-sign-total int16 R
0x0074 (116)holdingPF-sign-a int16 R
0x0075 (117)holdingPF-sign-b int16 R
0x0076 (118)holdingPF-sign-c int16 R
0x0077 (119)holdingkW-total int16 R
0x0078 (120)holdingkVAR-total int16 R
0x0079 (121)holdingkVA-total int16 R
0x007A (122)holdingkW-a int16 R
0x007B (123)holdingkW-b int16 R
0x007C (124)holdingkW-c int16 R
0x007D (125)holdingkVAR-a int16 R
0x007E (126)holdingkVAR-b int16 R
0x007F (127)holdingkVAR-c int16 R
0x0080 (128)holdingkVA-a int16 R
0x0081 (129)holdingkVA-b int16 R
0x0082 (130)holdingkVA-c int16 R
0x0083 (131)holdingkW-demand int16 R
0x0084 (132)holdingkW-peak-demand int16 R
0x0085 (133)holdingkVAR-demand int16 R
0x0086 (134)holdingkVA-demand int16 R
0x0087 (135)holdingkVAR-peak-demand int16 R
0x0088 (136)holdingkVA-peak-demand int16 R
0x0089 (137)holdingkWh-del uint32 ×2 R
0x008B (139)holdingkWh-rec uint32 ×2 R
0x008D (141)holdingkVARh-del uint32 ×2 R