electric-powerlogic-ion7550-ion7650

Autre RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0095 (149)holdingI-a,-Amp/freq/unbal uint16 R
0x0096 (150)holdingI-b,-Amp/freq/unbal uint16 R
0x0097 (151)holdingI-c,-Amp/freq/unbal uint16 R
0x0098 (152)holdingI-4,-Amp/freq/unbal uint16 R
0x0099 (153)holdingI-5,-Amp/freq/unbal uint16 R
0x009A (154)holdingI-avg,-Amp/freq/unbal uint16 R
0x009B (155)holdingI-avg-mn,-Amp/freq/unbal uint16 R
0x009C (156)holdingI-avg-mx,-Amp/freq/unbal uint16 R
0x009D (157)holdingI-avg-mean,-Amp/freq/unbal uint16 R
0x009E (158)holdingFreq,-Amp/freq/unbal uint16 R
0x009F (159)holdingFreq-mn,-Amp/freq/unbal uint16 R
0x00A0 (160)holdingFreq-mx,-Amp/freq/unbal uint16 R
0x00A1 (161)holdingFreq-mean,-Amp/freq/unbal uint16 R
0x00A2 (162)holdingV-unbal,-Amp/freq/unbal uint16 VR
0x00A3 (163)holdingI-unbal,-Amp/freq/unbal uint16 R
0x00A4 (164)holdingPhase-Rev,-Amp/freq/unbal uint16 R
0x00A5 (165)holdingVln-a,-Volts uint32 ×2 R
0x00A7 (167)holdingVln-b,-Volts uint32 ×2 R
0x00A9 (169)holdingVln-c,-Volts uint32 ×2 R
0x00AB (171)holdingVln-avg,-Volts uint32 ×2 R
0x00AD (173)holdingVln-avg-mx,-Volts uint32 ×2 R
0x00B1 (177)holdingVll-ab,-Volts uint32 ×2 R
0x00B3 (179)holdingVll-bc,-Volts uint32 ×2 R
0x00B5 (181)holdingVll-ca,-Volts uint32 ×2 R
0x00B7 (183)holdingVll-avg,-Volts uint32 ×2 R
0x00B9 (185)holdingVll-avg-mx,-Volts uint32 ×2 R
0x00BB (187)holdingVll-avg-mean,-Volts uint32 ×2 R
0x00C5 (197)holdingkW-a,-kW/kVAr/kVA int32 ×2 kWR
0x00C7 (199)holdingkW-b,-kW/kVAr/kVA int32 ×2 kWR
0x00C9 (201)holdingkW-c,-kW/kVAr/kVA int32 ×2 kWR
0x00CB (203)holdingkW-tot,-kW/kVAr/kVA int32 ×2 kWR
0x00CD (205)holdingkW-tot-mx,-kW/kVAr/kVA int32 ×2 kWR
0x00CF (207)holdingkVAR-a,-kW/kVAr/kVA int32 ×2 kVARR
0x00D1 (209)holdingkVAR-b,-kW/kVAr/kVA int32 ×2 kVARR
0x00D3 (211)holdingkVAR-c,-kW/kVAr/kVA int32 ×2 kVARR
0x00D5 (213)holdingkVAR-tot,-kW/kVAr/kVA int32 ×2 kVARR
0x00D7 (215)holdingkVAR-tot-mx,-kW/kVAr/kVA int32 ×2 kVARR
0x00D9 (217)holdingkVA-a,-kW/kVAr/kVA int32 ×2 kVAR
0x00DB (219)holdingkVA-b,-kW/kVAr/kVA int32 ×2 kVAR
0x00DD (221)holdingkVA-c,-kW/kVAr/kVA int32 ×2 kVAR
0x00DF (223)holdingkVA-tot,-kW/kVAr/kVA int32 ×2 kVAR
0x00E1 (225)holdingkVA-tot-mx,-kW/kVAr/kVA int32 ×2 kVAR
0x00E5 (229)holdingkWh-del,-kWh/kVArh int32 ×2 kWhR
0x00E7 (231)holdingkWh-rec,-kWh/kVArh int32 ×2 kWhR
0x00E9 (233)holdingkVARh-del,-kWh/kVArh int32 ×2 kVARhR
0x00EB (235)holdingkVARh-rec,-kWh/kVArh int32 ×2 kVARhR
0x00ED (237)holdingkVAh-del+rec,-kWh/kVArh int32 ×2 kVArhR
0x0105 (261)holdingPF-sign-a,-PF/THD/Kfactor int16 R
0x0106 (262)holdingPF-sign-b,-PF/THD/Kfactor int16 R
0x0107 (263)holdingPF-sign-c,-PF/THD/Kfactor int16 R