Briques techniques

gtbmodbus

Catalogue Modbus

Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.

  • rtu
  • tcp
  • registres

siemens

sentron-pac-2200

Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0001 (1)holdingVoltage-VL1-N float32 ×2 VR
0x0003 (3)holdingVoltage-vlz float32 ×2 VR
0x0005 (5)holdingVoltage-vl-N float32 ×2 VR
0x0007 (7)holdingVoltage-VL1-L2 float32 ×2 VR
0x0009 (9)holdingVoltage-vlz-L3 float32 ×2 VR
0x000B (11)holdingVoltage-vl-L1 float32 ×2 VR
0x000D (13)holdingCurrent-L1 float32 ×2 AR
0x000F (15)holdingCurrent-L2 float32 ×2 AR
0x0011 (17)holdingCurrent-L3 float32 ×2 AR
0x0013 (19)holdingApparent-power-L1 float32 ×2 VAR
0x0015 (21)holdingApparent-power-L2 float32 ×2 VAR
0x0017 (23)holdingApparent-power-L3 float32 ×2 VAR
0x0019 (25)holdingActive-power-L1 float32 ×2 WR
0x001B (27)holdingActive-power-L2 float32 ×2 WR
0x001D (29)holdingActive-power-L3 float32 ×2 WR
0x001F (31)holdingReactive-power-L1 float32 ×2 varR
0x0021 (33)holdingReactive-power-L2 float32 ×2 varR
0x0023 (35)holdingReactive-power-L3 float32 ×2 varR
0x0025 (37)holdingPower-factor-L1 float32 ×2 R
0x0027 (39)holdingPower-factor-L2 float32 ×2 R
0x0029 (41)holdingPower-factor-L3 float32 ×2 R
0x0037 (55)holdingFrequency float32 ×2 HzR
0x0039 (57)holdingAverage-voltage-V-L-N float32 ×2 VR
0x003B (59)holdingAverage-voltage-V-L-L float32 ×2 VR
0x003D (61)holdingAverage-current float32 ×2 AR
0x003F (63)holdingTotal-apparent-power float32 ×2 VAR
0x0041 (65)holdingTotal-active-power float32 ×2 WR
0x0043 (67)holdingTotal-reactive-power float32 ×2 varR
0x0045 (69)holdingTotal-power-factor float32 ×2 R
0x00CD (205)holdingDevice-diagnostics-and-device-status uint32 ×2 R
0x00CF (207)holdingStatus-of-the-digital-outputs uint32 ×2 R
0x00D1 (209)holdingStatus-of-the-digital-inputs uint32 ×2 R
0x00D3 (211)holdingActive-tariff uint32 ×2 R
0x00D7 (215)holdingUniversal-counter uint32 ×2 R
0x00D9 (217)holdingRelevant-parameter-changes-counter uint32 ×2 R
0x00DB (219)holdingCounter-all-parameter-changes uint32 ×2 R
0x01F5 (501)holdingCumulated-active-power-import float32 ×2 WR
0x01F7 (503)holdingCumulated-reactive-power-import float32 ×2 varR
0x01F9 (505)holdingCumulated-active-power-export float32 ×2 WR
0x01FB (507)holdingCumulated-reactive-power-export float32 ×2 varR
0x01FD (509)holdingMaximum-active-power-reading-during-the-period float32 ×2 WR
0x01FF (511)holdingMinimum-active-power-reading-during-the-period float32 ×2 WR
0x0201 (513)holdingMaximum-reactive-power-reading-dur-ing-the-period float32 ×2 varR
0x0203 (515)holdingMinimum-reactive-power-reading-dur-ing-the-period float32 ×2 varR
0x0205 (517)holdingLength-of-the-current-measuring-period uint32 ×2 sR
0x0207 (519)holdingTime-since-start-of-the-active-demand-period uint32 ×2 sR
0x0321 (801)holdingActive-energy-import-tariff-1 float64 ×4 WhR
0x0325 (805)holdingActive-energy-import-tariff-2 float64 ×4 WhR
0x0329 (809)holdingActive-energy-export-tariff-1 float64 ×4 WhR
0x032D (813)holdingActive-energy-export-tariff-2 float64 ×4 WhR

Source

upstream : jibrilsharafi · fba9d46

doc d'origine

Calculs effectués localement dans votre navigateur. Aucune donnée envoyée sur nos serveurs.