Briques techniques

gtbmodbus

Catalogue Modbus

Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.

  • rtu
  • tcp
  • registres

veris

e23

Autre RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0601 (1537)holdingReal-energy-(ph)-consumption float32 ×2 kWhR
0x0603 (1539)holdingReactive-energy-(qh)-consumption float32 ×2 kVARhR
0x0605 (1541)holdingApparent-energy-(sh)-consumption float32 ×2 kVAhR
0x0607 (1543)holdingTotal-instantaneous-real-power-(p) float32 ×2 kWR
0x0609 (1545)holdingTotal-instantaneous-reactive-power-(q) float32 ×2 kVARR
0x060B (1547)holdingTotal-instantaneous-apparent-power-(s) float32 ×2 kVAR
0x060D (1549)holdingAverage-power-factor-(pf:-total-kw-/-total-kva) float32 ×2 RatioR
0x060F (1551)holdingVoltage-line-to-line-(u),-average-of-active-phases float32 ×2 VoltR
0x0611 (1553)holdingVoltageline-to-neutral-(v),-average-of-active-phases float32 ×2 VoltR
0x0613 (1555)holdingCurrent,-average-of-active-phases float32 ×2 AmpR
0x0615 (1557)holdingFrequency-(derived-from-phase-a,-b,-or-C-in-that-order) float32 ×2 HzR
0x0617 (1559)holdingTotal-real-power-present-demand float32 ×2 kWR
0x0619 (1561)holdingTotal-reactive-power-present-demand float32 ×2 kVARR
0x061B (1563)holdingTotal-apparent-power-present-demand float32 ×2 kVAR
0x061D (1565)holdingTotal-real-power-max-demand float32 ×2 kWR
0x061F (1567)holdingTotal-reactive-power-max-demand float32 ×2 kVARR
0x0621 (1569)holdingTotal-apparent-power-max-demand float32 ×2 kVAR
0x0629 (1577)holdingPulse-counter-1-(real-energy) float32 ×2 R
0x062B (1579)holdingPulse-counter-2-(reactive-energy) float32 ×2 R
0x0635 (1589)holdingReal-energy-consumption,-L1 float32 ×2 kWhR
0x0637 (1591)holdingReal-energy-consumption,-L2 float32 ×2 kWhR
0x0639 (1593)holdingReal-energy-consumption,-L3 float32 ×2 kWhR
0x063B (1595)holdingReactive-energy-consumption,-L1 float32 ×2 kWhR
0x063D (1597)holdingReactive-energy-consumption,-L2 float32 ×2 kWhR
0x063F (1599)holdingReactive-energy-consumption,-L3 float32 ×2 kWhR
0x0641 (1601)holdingApparent-energy-consumption,-L1 float32 ×2 kWhR
0x0643 (1603)holdingApparent-energy-consumption,-L2 float32 ×2 kWhR
0x0645 (1605)holdingApparent-energy-consumption,-L3 float32 ×2 kWhR
0x0647 (1607)holdingReal-power,-L1 float32 ×2 kWR
0x0649 (1609)holdingReal-power,-L2 float32 ×2 kWR
0x064B (1611)holdingReal-power,-L3 float32 ×2 kWR
0x064D (1613)holdingReactive-power,-L1 float32 ×2 kVARR
0x064F (1615)holdingReactive-power,-L2 float32 ×2 kVARR
0x0651 (1617)holdingReactive-power,-L3 float32 ×2 kVARR
0x0653 (1619)holdingApparent-power,-L1 float32 ×2 kVAR
0x0655 (1621)holdingApparent-power,-L2 float32 ×2 kVAR
0x0657 (1623)holdingApparent-power,-L3 float32 ×2 kVAR
0x0659 (1625)holdingPower-factor,-L1 float32 ×2 RatioR
0x065B (1627)holdingPower-factor,-L2 float32 ×2 RatioR
0x065D (1629)holdingPower-factor,-L3 float32 ×2 RatioR
0x065F (1631)holdingVoltage,-L1-L2 float32 ×2 VoltR
0x0661 (1633)holdingVoltage,-L2-L3 float32 ×2 VoltR
0x0663 (1635)holdingVoltage,-L3-L1 float32 ×2 VoltR
0x0665 (1637)holdingVoltage,-L1-N float32 ×2 VoltR
0x0667 (1639)holdingVoltage,-L2-N float32 ×2 VoltR
0x0669 (1641)holdingVoltage,-L3-N float32 ×2 VoltR
0x066B (1643)holdingCurrent,-phase-A float32 ×2 AmpR
0x066D (1645)holdingCurrent,-phase-B float32 ×2 AmpR
0x066F (1647)holdingCurrent,-phase-C float32 ×2 AmpR
0x0671 (1649)holdingCurrent,-neutral float32 ×2 AmpR

Source