Briques techniques

gtbmodbus

Catalogue Modbus

Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.

  • rtu
  • tcp
  • registres

veris

e34

Compteur électrique RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x2775 (10101)holdingTotal-kwh-(msw) float32 ×2 kWhR
0x277D (10109)holdingTotal-kw float32 ×2 kWR
0x2781 (10113)holdingTotal-kva float32 ×2 kVAR
0x2783 (10115)holdingTotal-pf float32 ×2 PFR
0x2787 (10119)holdingAverage-current float32 ×2 AmperesR
0x2789 (10121)holdingPresent-kw-demand float32 ×2 kWR
0x278F (10127)holdingPresent-current-demand float32 ×2 AmperesR
0x2791 (10129)holdingMax-kw-demand float32 ×2 kWR
0x2797 (10135)holdingMax-current-demand float32 ×2 AmperesR
0x2799 (10137)holdingMax-kw float32 ×2 kWR
0x279F (10143)holdingMax-current float32 ×2 AmperesR
0x27A1 (10145)holdingVoltage,-L-l,-average-of-3-phases float32 ×2 VoltsR
0x27A3 (10147)holdingVoltage,-L-n,-average-of-3-phases float32 ×2 VoltsR
0x27A5 (10149)holdingFrequency-(derived-from-phase-a) float32 ×2 HertzR
0x27A7 (10151)holdingThd-current,-weighted-average-of-3-phases float32 ×2 R
0x27A9 (10153)holdingThd-voltage-L-l,-weighted-average-of-3-phases float32 ×2 R
0x27AB (10155)holdingThd-voltage-L-n,-weighted-average-of-3-phases float32 ×2 R
0x27AD (10157)holdingSnapshot-kwh-(msw) float32 ×2 kWhR
0x283D (10301)holdingKwh-(msw) float32 ×2 kWhR
0x2845 (10309)holdingKw float32 ×2 kWR
0x2849 (10313)holdingKva float32 ×2 kVAR
0x284B (10315)holdingPf float32 ×2 PFR
0x284D (10317)holdingCurrent-angle float32 ×2 degrees-angularR
0x284F (10319)holdingCurrent float32 ×2 AmperesR
0x2851 (10321)holdingPresent-kw-demand float32 ×2 kWR
0x2857 (10327)holdingPresent-current-demand float32 ×2 AmperesR
0x2859 (10329)holdingMax-kw-demand float32 ×2 kWR
0x285F (10335)holdingMax-current-demand float32 ×2 AmperesR
0x2861 (10337)holdingMax-kw float32 ×2 kWR
0x2867 (10343)holdingMax-current float32 ×2 AmperesR
0x2869 (10345)holdingVoltage,-L-L float32 ×2 VoltsR
0x286B (10347)holdingVoltage,-L-N float32 ×2 VoltsR
0x286D (10349)holdingFrequency-(derived-from-phase-a) float32 ×2 HertzR
0x286F (10351)holdingThd-current float32 ×2 R
0x2871 (10353)holdingThd-voltage-L-L float32 ×2 R
0x2873 (10355)holdingThd-voltage-L-N float32 ×2 R
0x2875 (10357)holdingKwh-snapshot-(msw) float32 ×2 kWhR
0x2905 (10501)holdingKwh-(msw) float32 ×2 kWhR
0x290D (10509)holdingKw float32 ×2 kWR
0x2911 (10513)holdingKva float32 ×2 kVAR
0x2913 (10515)holdingPf float32 ×2 PFR
0x2915 (10517)holdingCurrent-angle float32 ×2 degrees-angularR
0x2917 (10519)holdingCurrent float32 ×2 AmperesR
0x2919 (10521)holdingPresent-kw-demand float32 ×2 kWR
0x291F (10527)holdingPresent-current-demand float32 ×2 AmperesR
0x2921 (10529)holdingMax-kw-demand float32 ×2 kWR
0x2927 (10535)holdingMax-current-demand float32 ×2 AmperesR
0x2929 (10537)holdingMax-kw float32 ×2 kWR
0x292F (10543)holdingMax-current float32 ×2 AmperesR
0x2931 (10545)holdingVoltage,-L-L float32 ×2 VoltsR

Source

upstream : jibrilsharafi · fba9d46

doc d'origine

Calculs effectués localement dans votre navigateur. Aucune donnée envoyée sur nos serveurs.