Briques techniques

gtbmodbus

Catalogue Modbus

Catalogue ouvert de devices Modbus — registres, types, échelles, RTU/TCP.

  • rtu
  • tcp
  • registres

veris

e50

Autre RTU 50 registres À vérifier

À vérifier

  • Source upstream : tuto tiers, vérifier les registres
  • Pas de config RTU/TCP fournie en amont
  • Ordre d'octets (word order) non spécifié — défaut AB-CD, vérifier sur datasheet

Registres (50/50)

scaleunité
0x0001 (1)holdingReal-energy-consumption uint32 ×2 kWhR
0x0003 (3)holdingTotal-instantaneous-real-power-(3-phase-total) uint16 kWR
0x0004 (4)holdingTotal-instantaneous-reactive-power-(3-phase-total) uint16 kVARR
0x0005 (5)holdingTotal-instantaneous-apparent-power-(3-phase-total) uint16 KVAR
0x0006 (6)holdingTotal-power-factor-(total-kw-/total-kva) uint16 RatioR
0x0007 (7)holdingVoltage,-L-l,-average-of-3-phases uint16 VoltR
0x0008 (8)holdingVoltage,-L-ii,-average-of-3-phases uint16 VoltR
0x0009 (9)holdingCurrent,-average-of-3-phases uint16 AmpR
0x000A (10)holdingReal-power,-phase-A uint16 kWR
0x000B (11)holdingReal-power,-phase-B uint16 kWR
0x000C (12)holdingReal-power,-phase-C uint16 kWR
0x000D (13)holdingPower-factor,-phase-A uint16 RatioR
0x000E (14)holdingPower-factor,-phase-B uint16 RatioR
0x000F (15)holdingPower-factor,-phase-C uint16 RatioR
0x0010 (16)holdingVoltage,-phase-A-B uint16 VoltR
0x0011 (17)holdingVoltage,-phase-B-C uint16 VoltR
0x0012 (18)holdingVoltage,-phase-A-C uint16 VoltR
0x0013 (19)holdingVoltage,-phase-A-N uint16 VoltR
0x0014 (20)holdingVoltage,-phase-B-N uint16 VoltR
0x0015 (21)holdingVoltage,-phase-C-N uint16 VoltR
0x0016 (22)holdingCurrent,-instantaneous,-phase-A uint16 AmpR
0x0017 (23)holdingCurrent,-instantaneous,-phase-B uint16 AmpR
0x0018 (24)holdingLjrrent,-instantaneous,-phase-C uint16 AmpR
0x001A (26)holdingFrequency-(derived-from-phase-A) uint16 HzR
0x001F (31)holdingApparent-power-phase-A uint16 KVAR
0x0020 (32)holdingApparent-power-phase-B uint16 KVAR
0x0022 (34)holdingReactive-power,-phase-A uint16 kVARR
0x0023 (35)holdingReactive-power,-phase-B uint16 kVARR
0x0024 (36)holdingReactive-power,-phase-C uint16 kVARR
0x0025 (37)holdingTotal-real-power-present-demand uint16 kWR
0x0026 (38)holdingTotal-reactive-power-present-demand uint16 kVARR
0x0027 (39)holdingTotal-apparent-power-present-demand uint16 KVAR
0x0028 (40)holdingTotal-real-power-max-demand uint16 kWR
0x0029 (41)holdingTotal-reactive-power-max-demand uint16 kVARR
0x002A (42)holdingTotal-apparent-power-max-demand uint16 KVAR
0x0101 (257)holdingReal-energy-consumption-(clear-via-reset-register) float32 ×2 kWhR
0x0103 (259)holdingReal-energy-consumption-(clear-via-reset-register) float32 ×2 kWhR
0x0105 (261)holdingTotal-instantaneous-real-power float32 ×2 kWR
0x0107 (263)holdingTotal-instantaneous-reactive-power float32 ×2 kVAkR
0x0109 (265)holdingTotal-instantaneous-apparent-power float32 ×2 kVAR
0x010B (267)holdingTotal-power-factor-(total-kw-/-total-kva) float32 ×2 RatioR
0x0111 (273)holdingCurrent,-average-of-3-phases float32 ×2 AmpR
0x0113 (275)holdingReal-power-phase-A float32 ×2 kWR
0x0115 (277)holdingReal-power-phase-B float32 ×2 kWR
0x0117 (279)holdingReal-power-phase-C float32 ×2 kWR
0x0119 (281)holdingPower-factor-phase-A float32 ×2 RatioR
0x011B (283)holdingPower-factor-phase-B float32 ×2 RatioR
0x011D (285)holdingPower-factor-phase-C float32 ×2 RatioR
0x011F (287)holdingVoltage,-phase-A-B float32 ×2 VoltR
0x0121 (289)holdingVoltage,-phase-B-C float32 ×2 VoltR

Source

upstream : jibrilsharafi · fba9d46

doc d'origine