eBox Professional

Electricity meter RTUTCP 36 registers To check

To check

  • Ordre d'octets non spécifié — défaut AB-CD, vérifier sur datasheet

Source

upstream: ha-modbus-manager · 8932e9a

Writes

3

Scaled

2

Enums

0

Multi-register

19

Registers (36/36)

scaleunit
0x0000 (0)inputID · id string R
0x0019 (25)inputSerial Number · serial_number string R
0x0032 (50)inputActive Protocol · active_protocol string R
0x0064 (100)inputManufacturer · manufacturer string R
0x007D (125)inputPlatform Type · platform_type string R
0x0096 (150)inputProduct Type · product_type string R
0x00AF (175)inputModbus Table Version · modbus_table_version uint16 R
0x00C8 (200)inputFirmware · firmware string R
0x00E1 (225)inputNumber Of Sockets · number_of_sockets uint16 R
0x00FA (250)inputOcpp State · ocpp_state uint16 R
0x0113 (275)inputStatus · status string R
0x012C (300)inputCable Status · cable_status uint16 R
0x012D (301)inputVoltage Phase 1 · voltage_phase_1 float32 ×2 VR
0x012F (303)inputVoltage Phase 2 · voltage_phase_2 float32 ×2 VR
0x0131 (305)inputVoltage Phase 3 · voltage_phase_3 float32 ×2 VR
0x0133 (307)inputEnergy Meter Reading · energy_meter_reading float32 ×2 1kWhR
0x03E8 (1000)inputActual Max Current Phase 1 · actual_max_current_phase_1 float32 ×2 AR
0x03EA (1002)inputActual Max Current Phase 2 · actual_max_current_phase_2 float32 ×2 AR
0x03EC (1004)inputActual Max Current Phase 3 · actual_max_current_phase_3 float32 ×2 AR
0x03EE (1006)inputCurrent Phase 1 · current_phase_1 float32 ×2 AR
0x03F0 (1008)inputCurrent Phase 2 · current_phase_2 float32 ×2 AR
0x03F2 (1010)inputCurrent Phase 3 · current_phase_3 float32 ×2 AR
0x03F4 (1012)holdingMax Current Phase 1 · max_current_phase_1 float32 ×2 AR
0x03F4 (1012)holdingMax Current Phase 1 · max_current_phase_1 float32 ×2 AR/W
0x03F6 (1014)holdingMax Current Phase 2 · max_current_phase_2 float32 ×2 AR
0x03F6 (1014)holdingMax Current Phase 2 · max_current_phase_2 float32 ×2 AR/W
0x03F8 (1016)holdingMax Current Phase 3 · max_current_phase_3 float32 ×2 AR
0x03F8 (1016)holdingMax Current Phase 3 · max_current_phase_3 float32 ×2 AR/W
0x03FA (1018)holdingFallback Max Current Phase 1 · fallback_max_current_phase_1 float32 ×2 AR
0x03FC (1020)holdingFallback Max Current Phase 2 · fallback_max_current_phase_2 float32 ×2 AR
0x03FE (1022)holdingFallback Max Current Phase 3 · fallback_max_current_phase_3 float32 ×2 AR
0x0400 (1024)holdingRemaining Time Before Fallback · remaining_time_before_fallback uint16 1sR
0x0401 (1025)holdingStation Phase Setup L1 · station_phase_setup_l1 uint16 R
0x0402 (1026)holdingStation Phase Setup L2 · station_phase_setup_l2 uint16 R
0x0403 (1027)holdingStation Phase Setup L3 · station_phase_setup_l3 uint16 R
0x0404 (1028)holdingAvailability · availability uint16 R